 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 THIS COMMENT FROM THE PREVIOUS REVIEW.
  
 #3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND
 106.3.5.4(8) FBC. ALL PANELS. THIS COMMENT IS NOW IN
 REFERENCE TO PANEL "C".
  
 NEW COMMENT THAT IS NOW BROUGHT BY INCREASING THE
 SERVICE TO 400 AMPS.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, 1/0 CU MINIMUM.
  
 2} THE MAIN HOUSE GROUND IS SHOWN AT THE INTERIOR PANEL
 "H", INSTEAD AT THE DISCONNECT OUTSIDE. THE GEC IS
 REQUIRED TO BE AT THE DISCONNECT OF A SEPARATE
 STRUCTURE, NOT ON THE LOAD SIDE. SEE 250.30(A).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  