Plan Review Notes For Permit 07070140 |
Permit Number |
07070140 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-13 13:42:47 | *** DENIED *** | | 1) SEE ELECTRICAL REVIEW #1 REGARDING RAISED SEAL, | | PLEASE CORRECT. | | | | 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | 13-101.2.2. | | | | 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004 | | FBC 13-607.1.ABC.1. | | | | 4) MAIN SUPPLY AIR DUCT (FLEX) FROM AHU TO THE MIXING | | BOX NEEDS TO BE SIZED. | | | | 5) NEED TO SHOW CLOTHES DRYER VENT ON MECHANICAL PLANS, | | SEE 2004 FBC/R M1501. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|