Plan Review Notes
Plan Review Notes For Permit 07070140
Permit Number 07070140
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-13 13:42:47*** DENIED ***
 1) SEE ELECTRICAL REVIEW #1 REGARDING RAISED SEAL,
 PLEASE CORRECT.
  
 2) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.2.
  
 3) PLEASE SUBMIT COOLING LOAD CALCULATIONS, SEE 2004
 FBC 13-607.1.ABC.1.
  
 4) MAIN SUPPLY AIR DUCT (FLEX) FROM AHU TO THE MIXING
 BOX NEEDS TO BE SIZED.
  
 5) NEED TO SHOW CLOTHES DRYER VENT ON MECHANICAL PLANS,
 SEE 2004 FBC/R M1501.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.