Plan Review Notes For Permit 07070140 |
Permit Number |
07070140 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-12 07:27:06 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW | | | | 1} THE ARCHITECTS SEAL IS INDISCERNIBLE. SEE | | 61G1-16.001FAC. | | | | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO | | BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 | | NEC 2005. | | | | 3} SUBMIT A PANEL SCHEDULE PER 408.4 NEC AND | | 106.3.5.4(8) FBC. ALL PANELS. | | | | 4} R313.1.1 SMOKE ALARMS SHALL BE LOCATED AS REQUIRED | | IN NEW DWELLINGS WHEN REPAIRS OR ADDITIONS REQUIRING A | | PERMIT OCCUR. SEE ARTICLE FOR COMPLETE TEXT. LOCATE ON | | THE PLAN. | | | | 5} LOCATE RECEPTACLES AS REQUIRED PER 210.52(D) IN THE | | 2ND FLOOR BATHROOMS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|