2007-07-24 10:46:11 | DENIED BY BUILDING |
| |
| 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT |
| MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 2)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS. |
| EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM) |
| SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE |
| RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL |
| NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM |
| AN ADJACENT PROJECTION OR WALL. SPECIFY THE DISTANCE TO |
| THE CARRAIGE HOUSE AND STRUCTURES ON THE ADJACENT LOTS |
| WHERE THE DISTANCE TO THE PROPERTY LINE IS LESS THAN 6 |
| FEET. |
| |
| 4) SUBMIT ENERGY CALCULATIONS FOR THE REMODELED |
| CARRIAGE HOUSEAS REQUIRED BY FBC CHAPTER 13. |
| |
| 5) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND |
| INSTALLATION INSTRUCTIONS FOR THE ICYNENE INSULATION. |
| |
| 6) SHOW COMPLIANCE WITH FBC R320 PROTECTION AGAINST |
| TERMITES. SPECIFY WHAT METHOD OF TERMITE PROTECTION |
| WILL BE USED. |
| |
| 7)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST DECAY |
| AND TERMITES. |
| CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT |
| LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL, |
| WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR |
| SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON |
| ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM) |
| HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON |
| A ROOF ABOVE ANOTHER ROOF. |
| |
| 8)IN ORDER FOR THE EXTERIOR DOORS OR WINDOWS TO BE |
| REUSED THEY ARE REQUIRED TO HAVE A PRODUCT APPROVAL OR |
| HAVE SITE SPECIFIC ENGINEERING. INDICATE WHICH PRODUCT |
| APPROVALS ARE FOR THESE ITEMS OR SUBMIT SIGNED AND |
| SEALED ENGINEERING FOR THEM. IMPACT PROTECTION IS ALSO |
| REQUIRED FOR THESE PRODUCTS. |
| |
| 9) SPECIFY THE WINDOW TYPES ON THE PLANS(IE. SINGLE |
| HUNG, CASEMENT, ETC.). |
| |
| 10) SPECIFY THE DOOR TYPE OF THE SIDE SWING DOOR AT THE |
| GARAGE ON THE FIRST FLOOR PLAN ON CH.2. SUBMIT PRODUCT |
| APPROVALS FOR THIS DOOR. THE DOOR IS NOT SHOWN ON THE |
| PROPOSED EAST ELEVATION ONCH.4. |
| |
| 11) SHOW COMPLIANCE WITH R322.1.1 FOR BATHROOM DOOR |
| WITH A 29" CLEAR OPENING. |
| |
| 12) ON SHEET S.1 THE NOTES REFERENCE ASCE 7-98. PLEASE |
| UPDATE THIS TO REFERENCE ASCE 7-02 PER CHAPTER 43 OF |
| THE 2004 FBC RESIDENTIAL. |
| |
| 13) ALSO ON SHEET S.1, PLEASE UPDATE ASCE 530-99 TO |
| ASCE 530-05. SEE FBC R CHAPTER 43. |
| |
| 14) ON SHEET S.1 THE NOTES SPECIFY REQUIRED SOIL |
| BEARING PRESSURE AS 3000 PSF. THE NOTE ON S.2 SPECIFIES |
| THE REQUIRED SOIL BEARING PRESSURE AS 2500 PSF. PLEASE |
| CORRECT. NOTE: THE SOIL ENGINEER'S REPORT IS FOR A SOIL |
| BEARING CAPACITY OF 2500 PSF. |
| |
| 15) PROVIDE DETAILS FOR THE INTERIOR STAIRS. SHOW |
| COMPLIANCE WITH FBC R311.5. SPECIFY RISER AND TREAD |
| DIMENSIONS, HANDRAILS, GUARDS, ETC. |
| |
| 16) SPECIFY THE SLOPE OF THE PORCH ROOF. |
| |
| 17) SPECIFY THE EMBED DEPTH OF THE #5 REBAR THAT IS |
| DOWELED AND EPOXIEDINTO THE EXISTING SLAB. SEE |
| FOUNDATION PLAN ON S.2. |
| |
| 18) SPECIFY THE HEIGHT OF THE PORCH ABOVE FINISH |
| GRADE. |
| |
| 19) PROVIDE A DETAIL FOR THE FIRST FLOOR JOISTS ATTACH |
| TO THE EXISTING FOUNDATION WALL. SEE THE FOUNDATION |
| PLAN ON S.2 WHERE THE B CONNECTORS ARE SPECIFIED. |
| |
| 20) DETAIL 2 ON S.2 SPECIFIES THE FOOTING DEPTH AS 1'- |
| 2" AND THE FOOTING SCHEDULE SPECIFIES THE DEPTH AS 18" |
| OR 1'- 6". PLEASE CORRECT. |
| |
| 21) PROVIDE BASE AND CAP CONNECTION DETAILS FOR THE 6 X |
| 6 WOOD POSTS AT THE PORCH. |
| |
| 22) PROVIDE DETAILS FOR THE WOOD BEAM AT THE PORCH. |
| SPECIFY THE CONNECTION OF THE WOOD BEAM TO THE WOOD |
| FRAME WALLS. |
| |
| 23) SPECIFY THE CONNECTION OF THE PORCH RAFTERS TO THE |
| WALLS OF THE STRUCTURE. |
| |
| 24) SPECIFY THE CEILING MATERIAL THAT WILL BE USED ON |
| THE UNDERSIDE OF THE PORCH RAFTERS. |
| |
| 25) SPECIFY THE OVERHANG AT THE PORCH ROOF. |
| |
| 26) PLEASE INDICATE WHERE THE STEEL BEAM DETAILS 6, 7 |
| AND 8 ON S.3 WILL BE USED. |
| |
| 27) THE EXISTING EAST ELEVATION ON A.3 DOES NOT SHOW |
| THE TWO LAUNDRY ROOM WINDOWS. |
| |
| 28) ON THE PROPOSED EAST ELEVATION ON SHEET A.3 PLEASE |
| CLARIFY IF THE 19'- 2" IS THE CEILING (BOTTOM OF THE |
| TRUSSES) OR THE ROOF (TOP OF TRUSSES). SEE THE LOCATION |
| OF THE OVER FLOW SCUPPER. |
| |
| 29) PROVIDE A DETAIL SPECIFING HOW THE PARAPET WALLS |
| ARE CONNECTED TO THE ROOF TRUSSES AND THE WALLS BELOW. |
| SPECIFY CONNECTORS, SPACING, ETC. |
| |
| 30) SPECIFY WHERE THE 18" DEEP FLOOR TRUSSES IN DETAIL |
| 4 ON S.3 ARE USED. |
| |
| 31) ON DETAIL 2 OF THE 2ND FLOOR FRAMING PLAN ON S.3 |
| THE FLOOR TRUSSES ARE SPECIFIED AS ROOF TRUSSES. PLEASE |
| CORRECT. |
| |
| 32)WPB ADMIN CODE 106.3* PRODUCT |
| APPROVALS. THOSE PRODUCT WHICH ARE |
| REGULATED BY DCA RULE 9B-72 SHALL BE |
| REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |
| 33) SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING |
| OF THE GAF ROOFING MATERIAL AS ALLOWED BY LIMITATION |
| NUMBER 7 ON PAGE 32 OF THE NOA. THE DESIGN PRESSURE FOR |
| THE SPECIFIED SYSTEM AND FASTENING OPTION IS - 45 PSF. |
| THE COMPONENT AND CLADDING TABLE IN THE 2004 FBC |
| SPECIFIES UPLIFTS OF -59.2 PSF IN ROOF ZONE 2 AND -89 |
| PSF IN ZONE 3. |
| |
| 34) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING |
| FRENCH DOORS WITH SIDELITES. |
| |
| 35) SUBMIT PRODUCT APPROVALS FOR THE NEW CYPRESS ENTRY |
| DOOR. |
| |
| - ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |