Plan Review Notes
Plan Review Notes For Permit 07070140
Permit Number 07070140
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-24 10:46:11DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS.
 EXTERIOR WALLS SEPARATED BY LESS THAN 6 FEET (1828 MM)
 SHALL HAVE NOT LESS THAN A ONE-HOUR FIRE-RESISTIVE
 RATING WITH EXPOSURE FROM BOTH SIDES. PROJECTIONS SHALL
 NOT EXTEND TO A POINT CLOSER THAN 4 FEET (1220 MM) FROM
 AN ADJACENT PROJECTION OR WALL. SPECIFY THE DISTANCE TO
 THE CARRAIGE HOUSE AND STRUCTURES ON THE ADJACENT LOTS
 WHERE THE DISTANCE TO THE PROPERTY LINE IS LESS THAN 6
 FEET.
  
 4) SUBMIT ENERGY CALCULATIONS FOR THE REMODELED
 CARRIAGE HOUSEAS REQUIRED BY FBC CHAPTER 13.
  
 5) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE ICYNENE INSULATION.
  
 6) SHOW COMPLIANCE WITH FBC R320 PROTECTION AGAINST
 TERMITES. SPECIFY WHAT METHOD OF TERMITE PROTECTION
 WILL BE USED.
  
 7)SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST DECAY
 AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 8)IN ORDER FOR THE EXTERIOR DOORS OR WINDOWS TO BE
 REUSED THEY ARE REQUIRED TO HAVE A PRODUCT APPROVAL OR
 HAVE SITE SPECIFIC ENGINEERING. INDICATE WHICH PRODUCT
 APPROVALS ARE FOR THESE ITEMS OR SUBMIT SIGNED AND
 SEALED ENGINEERING FOR THEM. IMPACT PROTECTION IS ALSO
 REQUIRED FOR THESE PRODUCTS.
  
 9) SPECIFY THE WINDOW TYPES ON THE PLANS(IE. SINGLE
 HUNG, CASEMENT, ETC.).
  
 10) SPECIFY THE DOOR TYPE OF THE SIDE SWING DOOR AT THE
 GARAGE ON THE FIRST FLOOR PLAN ON CH.2. SUBMIT PRODUCT
 APPROVALS FOR THIS DOOR. THE DOOR IS NOT SHOWN ON THE
 PROPOSED EAST ELEVATION ONCH.4.
  
 11) SHOW COMPLIANCE WITH R322.1.1 FOR BATHROOM DOOR
 WITH A 29" CLEAR OPENING.
  
 12) ON SHEET S.1 THE NOTES REFERENCE ASCE 7-98. PLEASE
 UPDATE THIS TO REFERENCE ASCE 7-02 PER CHAPTER 43 OF
 THE 2004 FBC RESIDENTIAL.
  
 13) ALSO ON SHEET S.1, PLEASE UPDATE ASCE 530-99 TO
 ASCE 530-05. SEE FBC R CHAPTER 43.
  
 14) ON SHEET S.1 THE NOTES SPECIFY REQUIRED SOIL
 BEARING PRESSURE AS 3000 PSF. THE NOTE ON S.2 SPECIFIES
 THE REQUIRED SOIL BEARING PRESSURE AS 2500 PSF. PLEASE
 CORRECT. NOTE: THE SOIL ENGINEER'S REPORT IS FOR A SOIL
 BEARING CAPACITY OF 2500 PSF.
  
 15) PROVIDE DETAILS FOR THE INTERIOR STAIRS. SHOW
 COMPLIANCE WITH FBC R311.5. SPECIFY RISER AND TREAD
 DIMENSIONS, HANDRAILS, GUARDS, ETC.
  
 16) SPECIFY THE SLOPE OF THE PORCH ROOF.
  
 17) SPECIFY THE EMBED DEPTH OF THE #5 REBAR THAT IS
 DOWELED AND EPOXIEDINTO THE EXISTING SLAB. SEE
 FOUNDATION PLAN ON S.2.
  
 18) SPECIFY THE HEIGHT OF THE PORCH ABOVE FINISH
 GRADE.
  
 19) PROVIDE A DETAIL FOR THE FIRST FLOOR JOISTS ATTACH
 TO THE EXISTING FOUNDATION WALL. SEE THE FOUNDATION
 PLAN ON S.2 WHERE THE B CONNECTORS ARE SPECIFIED.
  
 20) DETAIL 2 ON S.2 SPECIFIES THE FOOTING DEPTH AS 1'-
 2" AND THE FOOTING SCHEDULE SPECIFIES THE DEPTH AS 18"
 OR 1'- 6". PLEASE CORRECT.
  
 21) PROVIDE BASE AND CAP CONNECTION DETAILS FOR THE 6 X
 6 WOOD POSTS AT THE PORCH.
  
 22) PROVIDE DETAILS FOR THE WOOD BEAM AT THE PORCH.
 SPECIFY THE CONNECTION OF THE WOOD BEAM TO THE WOOD
 FRAME WALLS.
  
 23) SPECIFY THE CONNECTION OF THE PORCH RAFTERS TO THE
 WALLS OF THE STRUCTURE.
  
 24) SPECIFY THE CEILING MATERIAL THAT WILL BE USED ON
 THE UNDERSIDE OF THE PORCH RAFTERS.
  
 25) SPECIFY THE OVERHANG AT THE PORCH ROOF.
  
 26) PLEASE INDICATE WHERE THE STEEL BEAM DETAILS 6, 7
 AND 8 ON S.3 WILL BE USED.
  
 27) THE EXISTING EAST ELEVATION ON A.3 DOES NOT SHOW
 THE TWO LAUNDRY ROOM WINDOWS.
  
 28) ON THE PROPOSED EAST ELEVATION ON SHEET A.3 PLEASE
 CLARIFY IF THE 19'- 2" IS THE CEILING (BOTTOM OF THE
 TRUSSES) OR THE ROOF (TOP OF TRUSSES). SEE THE LOCATION
 OF THE OVER FLOW SCUPPER.
  
 29) PROVIDE A DETAIL SPECIFING HOW THE PARAPET WALLS
 ARE CONNECTED TO THE ROOF TRUSSES AND THE WALLS BELOW.
 SPECIFY CONNECTORS, SPACING, ETC.
  
 30) SPECIFY WHERE THE 18" DEEP FLOOR TRUSSES IN DETAIL
 4 ON S.3 ARE USED.
  
 31) ON DETAIL 2 OF THE 2ND FLOOR FRAMING PLAN ON S.3
 THE FLOOR TRUSSES ARE SPECIFIED AS ROOF TRUSSES. PLEASE
 CORRECT.
  
 32)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 33) SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 OF THE GAF ROOFING MATERIAL AS ALLOWED BY LIMITATION
 NUMBER 7 ON PAGE 32 OF THE NOA. THE DESIGN PRESSURE FOR
 THE SPECIFIED SYSTEM AND FASTENING OPTION IS - 45 PSF.
 THE COMPONENT AND CLADDING TABLE IN THE 2004 FBC
 SPECIFIES UPLIFTS OF -59.2 PSF IN ROOF ZONE 2 AND -89
 PSF IN ZONE 3.
  
 34) SUBMIT PRODUCT APPROVALS FOR THE DOUBLE OUTSWING
 FRENCH DOORS WITH SIDELITES.
  
 35) SUBMIT PRODUCT APPROVALS FOR THE NEW CYPRESS ENTRY
 DOOR.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  