 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
  
 PREVIOUS COMMENT #2} PROVIDE A LOAD CALCULATION FOR
 THE ELECTRICAL SERVICE, INDICATING ALL EXISTING LOADS
 AND ALL LOADS TO BE IMPOSED BY THE ADDITION OF THE NEW
 EQUIPMENT. 215.5 NEC 2005.
 IT IS NOTED THAT THE LOAD CALCULATION SUBMITTED WITH
 APPLICATION #07070140 INCLUDES THE CARRIAGE HOUSE. FOR
 RECORD RETENTION PURPOSES IT MUST ALSO BE INCLUDED WITH
 THIS SET.
  
 NEW COMMENT THAT IS NOW BROUGHT BY INCREASING THE
 SERVICE TO 400 AMPS AND PROVIDING THE PANEL SCHEDULE
 FOR REVIEW.
  
 1} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, 1/0 CU MINIMUM.
  
 2} THE MAIN HOUSE GROUND IS SHOWN AT THE INTERIOR PANEL
 "H", INSTEAD AT THE DISCONNECT OUTSIDE. THE GEC IS
 REQUIRED TO BE AT THE DISCONNECT OF A SEPARATE
 STRUCTURE, NOT ON THE LOAD SIDE. SEE 250.30(A).
  
 3} PER 210.11(C)(1), THERE MUST BE 2 SMALL APPLIANCE
 CIRCUITS FOR THE KITCHEN. ONLY ONE APPEARS ON THE PANEL
 SCHEDULE.
  
 4} THERE IS NO SHEET CH.1 IN EITHER OF THE SUBMITTED
 SETS OF PLANS. SEE NOTE ON THE ELECTRICAL RISER
 REGARDING THIS COMMENT.
  
 5} THE SMOKE ALARMS MUST BE DRAWN IN BY THE DESIGNER OF
 RECORD. HAND DRAWN DEVICES ARE NOT ACCEPTABLE. 106.5
 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.