2007-08-29 07:10:47 | |
| |
| |
| THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| |
| THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 |
| FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH |
| THE FOLLOWING: |
| |
| PREVIOUS COMMENT #2} PROVIDE A LOAD CALCULATION FOR |
| THE ELECTRICAL SERVICE, INDICATING ALL EXISTING LOADS |
| AND ALL LOADS TO BE IMPOSED BY THE ADDITION OF THE NEW |
| EQUIPMENT. 215.5 NEC 2005. |
| IT IS NOTED THAT THE LOAD CALCULATION SUBMITTED WITH |
| APPLICATION #07070140 INCLUDES THE CARRIAGE HOUSE. FOR |
| RECORD RETENTION PURPOSES IT MUST ALSO BE INCLUDED WITH |
| THIS SET. |
| |
| NEW COMMENT THAT IS NOW BROUGHT BY INCREASING THE |
| SERVICE TO 400 AMPS AND PROVIDING THE PANEL SCHEDULE |
| FOR REVIEW. |
| |
| 1} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH |
| 250.66, 1/0 CU MINIMUM. |
| |
| 2} THE MAIN HOUSE GROUND IS SHOWN AT THE INTERIOR PANEL |
| "H", INSTEAD AT THE DISCONNECT OUTSIDE. THE GEC IS |
| REQUIRED TO BE AT THE DISCONNECT OF A SEPARATE |
| STRUCTURE, NOT ON THE LOAD SIDE. SEE 250.30(A). |
| |
| 3} PER 210.11(C)(1), THERE MUST BE 2 SMALL APPLIANCE |
| CIRCUITS FOR THE KITCHEN. ONLY ONE APPEARS ON THE PANEL |
| SCHEDULE. |
| |
| 4} THERE IS NO SHEET CH.1 IN EITHER OF THE SUBMITTED |
| SETS OF PLANS. SEE NOTE ON THE ELECTRICAL RISER |
| REGARDING THIS COMMENT. |
| |
| 5} THE SMOKE ALARMS MUST BE DRAWN IN BY THE DESIGNER OF |
| RECORD. HAND DRAWN DEVICES ARE NOT ACCEPTABLE. 106.5 |
| FBC AS AMENDED. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLAN REVIEW. |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |