Plan Review Notes
Plan Review Notes For Permit 07070138
Permit Number 07070138
Review Stop B
Sequence Number 2
Notes
Date Text
2007-09-24 17:54:132004 FBC W/2007 SUPPLEMENT
 LEVEL 2 ALTERATION AND ADDITION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) THE INDEX ON SHEET CH.O DOES NOT LIST SHEETS
 CHMEP.1, CHS.1 OR CHS.2.
  
 3) SHEET CH.1 IS MISSING FROM THE PLANS.
  
 4) THE ENERGY CALCULATION LISTS TWO BEDROOMS AND ONLY
 ONE IS SHOWN ON THE PLANS. PLEASE CORRECT.
  
 5) ITEM #7 FROM THE FIRST REVIEW HAS NOT BEEN
 ADDRESSED. THE EXIT DOOR IS REQUIRED TO PROVIDE DIRECT
 ACCESS FROM THE HABITABLE PORTION OF THE DWELLING TO
 THE EXTERIOR. ONE LEAF OF THE DOUBLE DOOR AT THE LIVING
 ROOM IS REQUIRED TO BE 36" WIDE PER FBC R 311.4.2.
  
 6) ITEM #9 FROM THE FIRST REVIEW HAS NOT BEEN
 ADDRESSED. SPECIFY THE WINDOW TYPES ON THE PLANS.
 FBC*106.1.2.
  
 7) HANDWRITTEN CORRECTIONS TO SIGNED AND SEALED
 DRAWINGS CAN ONLY BE MADE BY THE DESIGNER OF RECORD.
 THEY ARE REQUIRED TO BE SIGNED AND DATED. FS 481.
  
 8) RESPONSE TO ITEM 25, CONTRACTOR TO SUBMIT RAS 117
 CALCULATIONS UNDER A SEPARATE ROOFING PERMIT.
  
 -ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  