Plan Review Notes
Plan Review Notes For Permit 07070138
Permit Number 07070138
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-23 14:31:38DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) ON THE FIRST FLOOR DEMOA PLAN THE PROPOSED GUEST
 ROOM APPEARS TO BE PART OF THE EXISTING GARAGE AND NOT
 LIVING SPACE. IF THIS AREA IS BEING COVERTED TO LIVING
 SPACE, THEN COUNTY IMPACTY FEES MAY BE DUE. PLEASE
 CLARIFY. IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SHOW COMPLIANCE WITH R309.2 SEPARATION REQUIRED. THE
 GARAGE SHALL BE SEPARATED FROM THE RESIDENCE AND ITS
 ATTIC AREA BY NOT LESS THAN 1/2 -INCH (12.7 MM) GYPSUM
 BOARD APPLIED TO THE GARAGE SIDE. GARAGES BENEATH
 HABITABLE ROOMS SHALL BE SEPARATED FROM ALL HABITABLE
 ROOMS ABOVE BY NOT LESS THAN 5 / 8 -INCH (15.9 MM) TYPE
 X GYPSUM BOARD OR EQUIVALENT. WHERE THE SEPARATION IS A
 FLOOR-CEILING ASSEMBLY, THE STRUCTURE SUPPORTING THE
 SEPARATION SHALL ALSO BE PROTECTED BY NOT LESS THAN
 1/2-INCH (12.7 MM) GYPSUM BOARD OR EQUIVALENT.
  
 4) SUBMIT ENERGY CALCULATIONS FOR THE REMODELED
 CARRIAGE HOUSEAS REQUIRED BY FBC CHAPTER 13.
  
 5) THE PROPOSED STRUCTURE IS LESS THAN 6 FEET FROM THE
 PROPERTY LINE. SPECIFY ON THE SITE PLAN THAT THE
 DISTANCE TO ANY STRUCTURES ON THE ADJACENT LOT AT THIS
 LOCATION IS GREATER THAN 6 FEET. SEE FBC R302.
  
 6) SHOW COMPLIANCE WITH FBC R320 PROTECTION AGAINST
 TERMITES. SPECIFY WHAT METHOD OF TERMITE PROTECTION
 WILL BE USED.
  
 7) SHOW COMPLIANCE WITH R311.4.1 EXIT DOOR REQUIRED AND
 R311.4.2 DOOR TYPE AND SIZE.
 NOT LESS THAN ONE EXIT DOOR CONFORMING TO THIS SECTION
 SHALL BE PROVIDED FOR EACH DWELLING UNIT. THE REQUIRED
 EXIT DOOR SHALL PROVIDE FOR DIRECT ACCESS FROM THE
 HABITABLE PORTIONS OF THE DWELLING TO THE EXTERIOR
 WITHOUT REQUIRING TRAVEL THROUGH A GARAGE. ACCESS TO
 HABITABLE LEVELS NOT HAVING AN EXIT IN ACCORDANCE WITH
 THIS SECTION SHALL BE BY A RAMP IN ACCORDANCE WITH
 SECTION R311.6 OR A STAIRWAY IN ACCORDANCE WITH SECTION
 R311.5 .
 THE REQUIRED EXIT DOOR SHALL BE A SIDE-HINGED DOOR NOT
 LESS THAN 3 FEET (914 MM) IN WIDTH AND 6 FEET 8 INCHES
 (2032 MM) IN HEIGHT. OTHER DOORS SHALL NOT BE REQUIRED
 TO COMPLY WITH THESE MINIMUM DIMENSIONS.
  
 8) SHOW COMPLIANCE WITH R320.7 PROTECTION AGAINST DECAY
 AND TERMITES.
 CONDENSATE LINES AND ROOF DOWNSPOUTS SHALL DISCHARGE AT
 LEAST 1 FOOT (305 MM) AWAY FROM THE STRUCTURE SIDEWALL,
 WHETHER BY UNDERGROUND PIPING, TAIL EXTENSIONS OR
 SPLASH BLOCKS. GUTTERS WITH DOWNSPOUTS ARE REQUIRED ON
 ALL BUILDINGS WITH EAVES OF LESS THAN 6 INCHES (152 MM)
 HORIZONTAL PROJECTION EXCEPT FOR GABLE END RAKES OR ON
 A ROOF ABOVE ANOTHER ROOF.
  
 9) SPECIFY THE WINDOW TYPES ON THE PLANS (IE. SINGLE
 HUNG, CASEMENT, ETC.).
  
 10) SPECIFY THE DOOR TYPE OF THE SIDE SWING DOOR AT THE
 GARAGE ON THE FIRST FLOOR PLAN ON CH.2. SUBMIT PRODUCT
 APPROVALS FOR THIS DOOR. THE DOOR IS NOT SHOWN ON THE
 PROPOSED EAST ELEVATION ONCH.4.
  
 11) SHOW COMPLIANCE WITH R322.1.1 FOR BATHROOM DOOR
 WITH A 29" CLEAR OPENING.
  
 12) ON SHEET S.1 THE NOTES REFERENCE ASCE 7-98. PLEASE
 UPDATE THIS TO REFERENCE ASCE 7-02 PER CHAPTER 43 OF
 THE 2004 FBC RESIDENTIAL.
  
 13) ALSO ON SHEET S.1, PLEASE UPDATE ASCE 530-99 TO
 ASCE 530-05. SEE FBC R CHAPTER 43.
  
 14) ON SHEET S.1 THE NOTES SPECIFY REQUIRED SOIL
 BEARING PRESSURE AS 3000 PSF. THE NOTE ON S.2 SPECIFIES
 THE REQUIRED SOIL BEARING PRESSURE AS 2500 PSF. PLEASE
 CORRECT. NOTE: THE SOIL ENGINEER'S REPORT IS FOR A SOIL
 BEARING CAPACITY OF 2500 PSF.
  
 15) SPECIFY THE SPACING AND LOCATIONS OF THE VERTICAL
 REINFORCEMENT FOR THE CONCRETE BLOCK WALLS AND
 PARAPET.
  
 16) SPECIFY THE HORIZONTAL REINFORCEMENT FOR THE U
 BLOCK AT THE TOP OF THE PARAPET.
  
 17) SPECIFY THE EMBED DEPTH OF THE 18" REBAR THAT IS
 DOWELED AND EPOXIEDINTO THE EXISTING SLAB.
  
 18) PROVIDE A DETAIL SHOWING HOW THE NEW BLOCK WALL AND
 TIE BEAMS WILL BE ATTACHED TO THE EXISTNG BLOCK WALL
 AND BEAMS.
  
 19) SPECIFY THE CONNECTORS THAT WILL BE USED TO SECURE
 THE TOPS OF THE 8 X 8 WOOD COLUMNS TO THE 4- 2 X 12
 WOOD BEAM.
  
 20) SPECIFY THE ATTACMENT OF THE 4-2 X 12 WOOD BEAM
 WITH THE EXTERIOR WALLS.
  
 21) PROVIDE A BUCK DETAIL FOR THE OVERHEAD GARAGE
 DOOR.
  
 22) PROVIDE A BUCK DETAIL FOR THE SIDE SWING DOORS.
  
 23)WPB ADMIN CODE 106.3* PRODUCT
 APPROVALS. THOSE PRODUCT WHICH ARE
 REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL.
  
 24) THE NOA FOR THE AMARR GARAGE DOOR IS EXPIRED.
 SUBMIT NOA NO. 07-0425.02, WHICH IS THE CURRENT NOA FOR
 THIS PRODUCT.
  
 25) SUBMIT RAS 117 CALCULATIONS FOR ENHANCED FASTENING
 OF THE GAF ROOFING MATERIAL AS ALLOWED BY LIMITATION
 NUMBER 7 ON PAGE 32 OF THE NOA. THE DESIGN PRESSURE FOR
 THE SPECIFIED SYSTEM AND FASTENING OPTION IS - 45 PSF.
 THE COMPONENT AND CLADDING TABLE IN THE 2004 FBC
 SPECIFIES UPLIFTS OF -59.2 PSF IN ROOF ZONE 2 AND -89
 PSF IN ZONE 3.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  
  