Plan Review Notes
Plan Review Notes For Permit 07070134
Permit Number 07070134
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-18 12:48:40 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW
  
 1} DECLARE OCCUPANCY TYPE FOR THIS BUILDING PER CHAPTER
 3, FLORIDA BUILDING CODE.
  
 2} DECLARE THE LEVEL OF ALTERATION THAT WAS DONE TO THE
 BUILDING PER 301.5 FBC EXISTING BUILDING CODE.
  
 3} PROVIDE A RISER DIAGRAM, INDICATE THE LOCATION OF
 THE SERVICE EQUIPMENT, NEW AND EXISTING.
  
 4} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5
 NEC 2005.
  
 5} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR
 DEVICES AND LIGHTING. SHOW COMPLIANCE WITH 700.12(F)(4)
 WHERE BATTERY PACK EMERGENCY LIGHTS ARE LOCATED.
  
 6} INDICATE WHAT EQUIPMENT THE "NEW DISCONNECTS" SHOWN
 ON THE PLAN SERVE.
  
 7} PROVIDE FORMS TO SHOW COMPLIANCE WITH CHAPTER 13
 FBC.PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER
 13-415.2.AND CERTIFICATION PER 13-103.1.2.
  
 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS PER 471FS ARE APPLICABLE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718