2007-07-18 12:48:40 | |
| |
| |
| NONCOMPLIANT |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW |
| |
| 1} DECLARE OCCUPANCY TYPE FOR THIS BUILDING PER CHAPTER |
| 3, FLORIDA BUILDING CODE. |
| |
| 2} DECLARE THE LEVEL OF ALTERATION THAT WAS DONE TO THE |
| BUILDING PER 301.5 FBC EXISTING BUILDING CODE. |
| |
| 3} PROVIDE A RISER DIAGRAM, INDICATE THE LOCATION OF |
| THE SERVICE EQUIPMENT, NEW AND EXISTING. |
| |
| 4} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL |
| SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO |
| BE IMPOSED BY THE ADDITION OF THE NEW EQUIPMENT. 215.5 |
| NEC 2005. |
| |
| 5} INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| DEVICES AND LIGHTING. SHOW COMPLIANCE WITH 700.12(F)(4) |
| WHERE BATTERY PACK EMERGENCY LIGHTS ARE LOCATED. |
| |
| 6} INDICATE WHAT EQUIPMENT THE "NEW DISCONNECTS" SHOWN |
| ON THE PLAN SERVE. |
| |
| 7} PROVIDE FORMS TO SHOW COMPLIANCE WITH CHAPTER 13 |
| FBC.PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER |
| 13-415.2.AND CERTIFICATION PER 13-103.1.2. |
| |
| 8} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| IF AN ARCHITECT OR ENGINEER, COMPLY WITH 418 AND 417 |
| FS, RESPECTIVELY. |
| THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL |
| IF EXEMPTIONS PER 471FS ARE APPLICABLE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |