Plan Review Notes
Plan Review Notes For Permit 07070098
Permit Number 07070098
Review Stop B
Sequence Number 3
Notes
Date Text
2007-08-27 13:02:36****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)YOU'VE DESIGNED THIS JOB TO -47.2 PSF.ENGINEER
 HAS SPECIFIED DESIGN PRESSURE OF -51.6.YOU HAVE
 CHANGED THE DESIGN PRESSURE ON THE INSTALLATION
 SCHEDULE BUT DID NOT CHANGE THE ANCHOR SPACING, SEE
 SHEET 7 OF THE PRODUCT APPROVAL.
  
 THE PLANS WERE RETURNED WITH NO CORRECTIONS AND NOTES
 STATING:"CORRECT NEGATIVE PRESSURE IS CIRCLED ON
 TABLE 1" AND "POSITIVE PRESSURES IS 36.5 ANCHOR
 SCHEDULE IS CORRECT."
  
 PLEASE SEE THE PRODUCT APPROVAL, SHEET 7, WHICH I HAVE
 HIGHLIGHTED.TABLE 1 IS A TABLE FOR ALLOWABLE SPANS
 PER DESIGN PRESSURE.YOU HAVE CIRCLED -52, MAX
 ALLOWABLE SPAN OF 11'6.THIS INFORMATION IS CODE
 COMPLIANT FOR THIS JOB AND WAS NOT MENTIONED IN MY
 PREVIOUS REVIEW.
  
 THE ANCHOR SCHEDULE ON SHEET 7 IS FOR NEGATIVE
 PRESSURES.YOU HAVE CIRCLED 47.2, BUT AS THE NEGATIVE
 PRESSURE FOR THIS JOB IS -51.6, YOU SHOULD BE USING THE
 77PSF ROW.IF I UNDERSTAND YOUR RESPONSE CORRECTLY,
 YOU ARE STATING THAT THE ANCHOR SCHEDULE IS FOR
 POSITIVE PRESSURES.THIS IS NOT CORRECT; THIS CHART IS
 TO BE USED FOR NEGATIVE PRESSURES AS THAT IS WORST
 CASE.PLEASE EITHER HAVE THE QUALIFIER CONTACT ME OR
 CONTACT THE ENGINEER FOR CLARIFICATION.
  