2007-08-21 07:19:30****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)YOU'VE DESIGNED THIS JOB TO -47.2 PSF.ENGINEER
 HAS SPECIFIED DESIGN PRESSURE OF -51.6.YOU HAVE
 CHANGED THE DESIGN PRESSURE ON THE INSTALLATION
 SCHEDULE BUT DID NOT CHANGE THE ANCHOR SPACING, SEE
 SHEET 7 OF THE PRODUCT APPROVAL.
  
 2.)PLEASE SEE THE NOTE AT THE BOTTOM OF THE
 INSTALLATION SCHEDULE - "ANCHOR TYPE MUST BE SPECIFIC,
 EG. THERE ARE DIFFERENT TYPES OF TAPCONS WITH DIFFERENT
 STRENGTH VALUES."THE INSTALLATION SCHEDULE STATES
 "1/4" TAPCON".THERE ARE TWO DIFFERENT 1/4" TAPCONS ON
 THE ANCHOR SCHEDULE.IN THIS CASE, IT APPEARS THAT YOU
 ARE SPECIFYING ANCHORING FOR THE MORE STRINGENT.IF
 THIS IS NOT THE CASE, SPECIFIC ANCHOR TYPE WILL BE
 REQUIRED ON THE INSTALLATION SCHEDULE.
  