Plan Review Notes
Plan Review Notes For Permit 07070088
Permit Number 07070088
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-27 08:46:06****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
  
 SHUTTER PERMIT APPLICATION, ONLY CHECKED ITEMS APPLY
  
 ____1.PROVIDE BUILDING HEIGHT ON THE PLAN.DESIGN
 PRESSURES FOR BUILDINGS OVER 60FEET ARE REQUIRED TO BE
 DESIGNED USING ASCE7, FBC1609.1.1 AND MUST BE DONE BY A
 DESIGN PROFESSIONAL. DOCUMENTS PREPARED BY AN ARCHITECT
 OR ENGINEER AND SUBMITTED FOR PUBLIC RECORD ARE TO BE
 SIGNED SEALED ORIGINALS FAC61G15, FAC61G1 16.
  
 ____2.PROVIDE A COPY OF THE CONDO ASSOCIATION
 APPROVAL.
  
 _XX_3.COMPLETE THE ATTACHED INSTALLATION SCHEDULE
 OR PROVIDE ALL INFORMATION TO SHOW CODE COMPLIANCE IN
 ANOTHER FORMAT.NOTE THAT THE FORM YOU HAVE PROVIDED
 LACKS THE FOLLOWING INFORMATION WHICH IS REQUIRED TO
 DETERMINE CODE COMPLIANCE FOR THIS JOB:SHUTTER TO
 GLASS SEPARATION, POSITIVE DESIGN PRESSURE.
  
 ____4.FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 REQUIRED, FAC9B72, WWW.FLORIDABUILDING.ORG.
  
 ____5.SHOW THE EMERGENCY MEANS OF ESCAPE, FBC
 R310.
  
 ____6.PROVIDE A FLOOR PLAN SHOWING WHERE THE
 SHUTTERS WILL BE INSTALLED AND PANEL SIZES WHICH
 CORRELATES WITH THE INSTALLATION SCHEDULE, ITEM 3
 ABOVE.
  
 ____8.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2),
 FBC R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE
 C HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.
  
  