2007-07-26 19:15:34****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)PROVIDE A FLOOR PLAN SHOWING LOCATION OF THE SGD'S
 AND WINDOWS.
  
 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED
 IN ADDITION TO THE NOA SUBMITTED, FAC9B72.
 WWW.FLORIDABUILDING.ORG
  
 SEE SHEET 1 OF 6 (DRAWINGS IN THE PRODUCT APPROVAL).A
 33% INCREASE IN ALLOWABLE STRESS WAS USED IN ANCHOR
 DESIGN.THIS IS NOT PERMITTED IN THE FLORIDA BUILDING
 CODE.IN ORDER FOR A LOCAL PRODUCT APPROVAL TO BE
 ISSUED USING THE NOA, SUBMIT A LETTER FROM THE ENGINEER
 STATING THAT THE ANCHORING IS ACCEPTABLE WITHOUT THE
 STRESS INCREASE, OR SUBMIT THE REVISED NOA.
  
 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER
 OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 4.)PROVIDE CONDO ASSOCIATION APPROVAL.
  
 5.)DOCUMENTS ARE NOT LEGIBLE, FBC*106.1.2.
  
 6.)THE WINDOWS DO NOT APPEAR TO BE COMPLIANT WITH THE
 DESIGN PRESSURES FOR THE BUILDING.