Plan Review Notes
Plan Review Notes For Permit 07070077
Permit Number 07070077
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-27 08:19:00 
  
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER
 230.70(A)(1)
  
 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH
 250.66, MINIMUM #4 CU FOR 2/0 SEC.
  
 3} PLEASE CHANGE THE NOTES TO INDICATE NFPA-72, AND
 NFPA-70, RATHER THAN MFPA AND MFP. ALSO NFPA-72 IS 2002
 EDITION.
  
 4} THE DINING ROOM RECEPTACLE CIRCUIT #27, MUST BE A 20
 AMP CIRCUIT PER 210.52(B)(1).
  
 5} THE WATER HEATER MUST HAVE A DISCONNECTING MEANS PER
 422.31(B), AND CAN NOT BE A RECEPTACLE AS SHOWN,
 422.16.
  
 6} THE DISCONNECTING MEANS LOCATED AT THE A/C EQUIPMENT
 (BOTH UNITS) DO NOT INDICATE COMPLIANCE WITH THE
 CLEARANCE REQUIREMENTS OF 110.26.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  