Plan Review Notes For Permit 07070077 |
Permit Number |
07070077 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-27 08:19:00 | | | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE | | COMPLIANCE AND RESUBMIT FOR REVIEW. | | | | 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED | | PER 230.70, 225.32. INDICATE LOCATION ON PLAN PER | | 230.70(A)(1) | | | | 2} THE GROUNDING ELECTRODE CONDUCTOR MUST COMPLY WITH | | 250.66, MINIMUM #4 CU FOR 2/0 SEC. | | | | 3} PLEASE CHANGE THE NOTES TO INDICATE NFPA-72, AND | | NFPA-70, RATHER THAN MFPA AND MFP. ALSO NFPA-72 IS 2002 | | EDITION. | | | | 4} THE DINING ROOM RECEPTACLE CIRCUIT #27, MUST BE A 20 | | AMP CIRCUIT PER 210.52(B)(1). | | | | 5} THE WATER HEATER MUST HAVE A DISCONNECTING MEANS PER | | 422.31(B), AND CAN NOT BE A RECEPTACLE AS SHOWN, | | 422.16. | | | | 6} THE DISCONNECTING MEANS LOCATED AT THE A/C EQUIPMENT | | (BOTH UNITS) DO NOT INDICATE COMPLIANCE WITH THE | | CLEARANCE REQUIREMENTS OF 110.26. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 |
|