Plan Review Notes
Plan Review Notes For Permit 07070066
Permit Number 07070066
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-26 16:16:05****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SPANS SHOULD BE BLADE LENGTH (ONE DIMENSION).
  
 2.)MINIMUM SPACING IS 3", SEE SHEET 7 (CANNOT SPECIFY
 2 1/2" SPACING).
  
 3.)SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE
 WITH ANCHOR SCHEDULES.YOU'VE HIGHLIGHTED "A" AND "I".
 REVISE INSTALLATION SCHEDULE; "HV" IS NOT A MOUNTING
 TYPE.
  
 4.)A AND I ARE FOR POURED CONCRETE SUBSTRATES ONLY.
 YOUR INSTALLATION SCHEDULE STATES THAT THIS ENTIRE JOB
 HAS A BLOCK SUBSTRATE.
  
 5.)9" SPACING WITH A .66 FACTOR REQURES 5.94" ANCHOR
 SPACING (CONCRETE SUBSTRATE, CONNECTION TYPE A, SEE
 PRODUCT APPROVAL).IT IS NOT CLEAR HOW YOU'VE
 DETERMINED THAT THE ANCHOR SPACING SHOULD BE 2 1/2".
  