Plan Review Notes For Permit 07070066 |
Permit Number |
07070066 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-08-26 16:16:05 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | 1.)SPANS SHOULD BE BLADE LENGTH (ONE DIMENSION). | | | | 2.)MINIMUM SPACING IS 3", SEE SHEET 7 (CANNOT SPECIFY | | 2 1/2" SPACING). | | | | 3.)SHUTTER CONNECTION MOUNTING TYPE SHOULD CORRELATE | | WITH ANCHOR SCHEDULES.YOU'VE HIGHLIGHTED "A" AND "I". | | REVISE INSTALLATION SCHEDULE; "HV" IS NOT A MOUNTING | | TYPE. | | | | 4.)A AND I ARE FOR POURED CONCRETE SUBSTRATES ONLY. | | YOUR INSTALLATION SCHEDULE STATES THAT THIS ENTIRE JOB | | HAS A BLOCK SUBSTRATE. | | | | 5.)9" SPACING WITH A .66 FACTOR REQURES 5.94" ANCHOR | | SPACING (CONCRETE SUBSTRATE, CONNECTION TYPE A, SEE | | PRODUCT APPROVAL).IT IS NOT CLEAR HOW YOU'VE | | DETERMINED THAT THE ANCHOR SPACING SHOULD BE 2 1/2". | | |
|