2007-07-26 18:07:29 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| 1.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER |
| OF RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), |
| FBC*106.3.3. |
| |
| 2.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL REQUIRED |
| IN ADDITION TO THE NOA SUBMITTED, FAC9B72. |
| WWW.FLORIDABUILDING.ORG |
| |
| 3.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, |
| BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION, |
| OCCUPANCY CLASSIFICATION FBC 3 AND AREA PER OCCUPANCY. |
| |
| 4.)DECLARE WIND DESIGN CRITERIA, FBC1603.1.4. |
| |
| 5.)SHOW HOW EGRESS IS AFFECTED BY THE ELIMINATION OF |
| THE DOOR. |
| |
| 6.)IMPACT PROTECTION IS REQUIRED, FBC1609.1.4. |
| |
| 7.)USE OF REMOVABLE SHUTTERS ON COMMERCIAL PROPERTIES |
| REQUIRES APPROVAL FROM THE BUILDING OFFICIAL.IF YOU |
| ARE PROPOSING TO USE REMOVABLE SHUTTERS, SUBMIT A |
| HURRICANE INSTALLATION PLAN, SEE ATTACHED POLICY, ITEM |
| 13.PROVIDE PRODUCT APPROVALS AND COMPLETE AN |
| INSTALLATION SCHEDULE. |
| |
| 8.)THE DOORS PROPOSED ARE NOT FOR USE WHERE WATER |
| INFILTRATION RESISTANCE IS REQUIRED.SHOW (ON THE |
| PLAN) WHY WATER INFILTRATION RESISTANCE IS NOT |
| REQUIRED.SEE FBC1714.5.2.1, EXCEPTIONS. |
| |
| 9.)PROVIDE PRODUCT APPROVALS FOR THE STOREFRONT. |
| |
| 10.)DETAIL A USES THE WORD "HUBGYGYVBGY".WHAT IS |
| THIS?THE PURPOSE OF PLANS IS TO SHOW CODE COMPLIANCE |
| OR FOR CONSTRUCTION.THE PURPOSE OF THIS NOTE IS NOT |
| CLEAR. |
| |
| 11.)THE PLAN SHOWS A 2X4 ALUMINUM TUBE, A GLASS |
| PANEL.WINDOWS ARE TO BE TESTED IN ACCORDANCE WITH |
| FBC1714.5.PLEASE MAKE SCOPE OF WORK AND |
| SPECIFICATIONS CLEAR ON THE PLAN. |
| |
| |
| |