2007-07-23 10:27:25DENIED;
 1. SANITARY RISER DIAGRAM;
 A) AUTOMATIC CLOTHES WASHERS ARE NOT PERMITED
 TO DUMP INTO A SANITARY CROSS SEFBC-2004 PLUMBING
 SECTION 706.3.
 B) LABLE ALL FIXTURES.
 C) EXPLAIN SANITARY STUB.
 D) LAUNDRY TUB NOT SHOWN.
 2. WATER RISER; SHOW WATER HAMMER ARRESTORS WHERE
 REQUIRED AND SPEC OUT SIZE AND MANUFATURE. SEE SECTION
 604.9
 3. PLUMBING NOTE # 8 PIPE2 1/2" AND SMALLER MUST PITCH
 1/4" PER FOOT. SEE TABLE 704.1.
 4. BREAK SINK MUST MEET THE REQUIREMENTS OF FBC-2004
 BUILDING CHAPTER 11 ACCESSIBITY CODE SEE SECTIONS;
 11-4.24.2 HEIGHT
 11-4.24.3 KNEE CLEARANCE UNDER SINK ( NO
 DOORS)
 11-4.24.4 DEPTH OF SINK. ( 6 1/2 DEEP MAX.
 11-4.24.5 CLEAR FLOOR SPACE SHOW ON PLANS.
 11-4.24.6 RAP EXPOSED PIPES.
 11-4.24.7 LEVER OPERATED FAUCETS.
 PLUMBING PLAN REVIEW BY
 JOHN LEECH