Plan Review Notes
Plan Review Notes For Permit 07070033
Permit Number 07070033
Review Stop M
Sequence Number 1
Notes
Date Text
2007-07-11 16:48:43*** DENIED ***
 1) PLEASE PROVIDE COMBUSTION AND MAKE-UP AIR, AND
 CALCULATIONS FOR GAS CLOTHES DRYERS AS THEY ARE IN A
 CONFINED SPACE, SEE 2004 FBC/FG 304.
  
 2) PLEASE RE-CALCULATE OUTSIDE AIR CALCULATIONS. MY
 CALCULATIONS SHOW THAT ZONE 1 REQUIRES 1,000 CFM'S,
 ZONE 2 REQUIRES 531 CFM'S, AND ZONE 3 REQUIRES 750
 CFM'S, SEE 2004 FBC/M TABLE 403.3 'SPECIALTY SHOPS'
 'BEAUTY' .
  
 3) SEE A/C SYSTEMS ON MECHANICAL PLANS ARE NOT LABELED
 CORRECT, CHECK THE WSHP SCHEDULE.
  
 4) SEE RETURN AIR GRILL FROM UNIT 2 IS COMMON DUCTED TO
 UNIT 3 GRILL ALSO AND THIS WOULD REQUIRE SMOKE DETECTOR
 IN THE SUPPLY AND RETURN DUCTS, PER 2004 FBC/M 606.2.2.
 IF THE ERV SUPPLIED OUTSIDE AIR TO UNIT 3 RETURN AIR
 GRILL THEN THE RETURNS WOULD NOT BE A COMMON RETURN AND
 NOT REQUIRE SMOKE DETECTORS IN THE RETURNS, ONLY THE
 SUPPLIES.
  
 5) PLEASE SHOW THE LOCATION OF THE DUCT SMOKE DETECTORS
 ON THE PLANS, ALSO THE ERV. SEE 2004 FBC/M 606.1.
  
 6) PLEASE LIST THE ERV IN THE EQUIPMENT SCHEDULE.
  
 7) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE
 ERV.
  
 8) PLEASE SHOW THE CFM'S FOR THE BATHROOM EXHAUST FANS
 ON THE MECHANICAL PLANS.
  
 9) THE FAN SCHEDULE IS SHOWING EF-2 AT 750 CFM'S, BUT
 IN THE NAILS ROOM IT SHOWS 1200 CFM'S, PLEASE CORRECT.
  
 10) IF EF-2 IS REMOVING 1200 CFM'S AND OUTSIDE AIR INTO
 THE BUILDING IS ONLY 650 CFM'S THE BUILDING WOULD BE IN
 A NEGATIVE PRESSURE, PLEASE CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.