2007-07-12 19:08:35 | PROJECT: 1551 NORTH FLAGLER DRIVE |
| |
| REVIEW: 2004 FLORIDA BUILDING CODE WITH 2006 REVISIONS |
| |
| STATUS: DENIED |
| |
| COMMENTS: |
| |
| |
| 1) PLEASE REVISE OCCUPANCY TYPE TO REFLECT BUSINESS |
| GROUP B AS PER THE FBC, SECTION 304.1. ALSO INDICATE |
| OCCUPANCY LOAD. |
| |
| 2) PLEASE REVISE THE INDICATED CONSTRUCTION TYPE. THIS |
| BUILDING WAS CONSTRUCTED AS A TYPE 1. |
| |
| 3) PLEASE INDICATE THE MECHANICAL ATTACHMENT OF THE |
| RUNNER CHANNEL TO THE EXISTING STRUCTURE. ALSO PROVIDE |
| CLARIFICATION OF EXISTING FRAMING MEMBER: WOOD OR STEEL |
| JOISTS. |
| |
| 4) SHOW MECHANICAL ATTACHMENT OF THE METAL FRAMING |
| DIAGONAL BRACING TO EXISTING STRUCTURE CONNECTION. SEE |
| DETAIL 1 ON SHEET A3 OF 8. |
| |
| 5) PROVIDE SPECIFICATIONS FOR CMU WALL INSULATION. |
| |
| 6) PLEASE SHOW FINISHED COUNTERTOP HEIGHTS ON FLOOR |
| PLAN, SHEET A1 OF 8. |
| |
| 7) PLEASE PROVIDE FIRE-STOPPING DETAILS IF APPLICABLE. |
| |
| 8) FIRE- BLOCKING SHALL CONFORM TO THE FOLLOWING: |
| |
| 717.1 GENERAL. |
| FIREBLOCKING AND DRAFTSTOPPING SHALL BE INSTALLED IN |
| COMBUSTIBLE CONCEALED LOCATIONS IN ACCORDANCE WITH THIS |
| SECTION. FIREBLOCKING SHALL COMPLY WITH SECTION 717.2. |
| DRAFTSTOPPING IN FLOOR/CEILING SPACES AND ATTIC SPACES |
| SHALL COMPLY WITH SECTIONS 717.3 AND 717.4, |
| RESPECTIVELY. THE PERMITTED USE OF COMBUSTIBLE |
| MATERIALS IN CONCEALED SPACES OF NONCOMBUSTIBLE |
| BUILDINGS SHALL BE LIMITED TO THE APPLICATIONS |
| INDICATED IN SECTION 717.5. |
| |
| 9) COMBUSTIBLES IN CONCEALED SPACES SHALL COMPLY WITH |
| THE FOLLOWING: |
| |
| 717.5 COMBUSTIBLES IN CONCEALED SPACES IN TYPE I OR II |
| CONSTRUCTION. |
| COMBUSTIBLES SHALL NOT BE PERMITTED IN CONCEALED SPACES |
| OF BUILDINGS OF TYPE I OR II CONSTRUCTION. |
| EXCEPTIONS: |
| 1. COMBUSTIBLE MATERIALS IN ACCORDANCE WITH SECTION |
| 603. |
| 2. COMBUSTIBLE MATERIALS COMPLYING WITH SECTION 602 OF |
| THE FLORIDA BUILDING CODE, MECHANICAL. |
| 3. CLASS A INTERIOR FINISH MATERIALS. |
| 4. COMBUSTIBLE PIPING WITHIN PARTITIONS OR ENCLOSED |
| SHAFTS INSTALLED IN ACCORDANCE WITH THE PROVISIONS OF |
| THIS CODE. COMBUSTIBLE PIPING SHALL BE PERMITTED WITHIN |
| CONCEALED CEILING SPACES WHERE INSTALLED IN ACCORDANCE |
| WITH THE FLORIDA BUILDING CODE, MECHANICAL AND THE |
| FLORIDA BUILDING CODE, PLUMBING. |
| |
| 10) FIRE RETARDANT TREATED LUMBER SHALL BE USED AS PER |
| THE FOLLOWING SECTION: |
| |
| 603.1 ALLOWABLE MATERIALS. |
| COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS |
| OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING |
| APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1 |
| THROUGH 603.1.3: |
| 1. FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN: |
| 1.1. NONBEARING PARTITIONS WHERE THE REQUIRED |
| FIRE-RESISTANCE RATING IS 2 HOURS OR LESS. |
| 1.2. NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS |
| REQUIRED. |
| 1.3. ROOF CONSTRUCTION AS PERMITTED IN TABLE 601, NOTE |
| C, ITEM 3. |
| |
| |