Plan Review Notes
Plan Review Notes For Permit 07070009
Permit Number 07070009
Review Stop B
Sequence Number 3
Notes
Date Text
2007-08-21 10:20:12****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
  
 FROM PREVIOUS LIST:
  
 1.)SEE INSTALLATION SCHEDULE.THE SHUTTER MOUNTING
 TYPE SHOULD STATE WHICH WALL CONNECTION YOU ARE USING.
 YOU HAVE HIGHLIGHTED BOTH WALL MOUNT 1 AND WALL MOUNT 3
 ON THE PRODUCT APPROVAL.WALL MOUNT 1 IS FOR CONCRETE
 SUBSTRATE ONLY, ALL OPENINGS ARE CONCRETE BLOCK PER
 INSTALLATION SCHEDULE.
  
 SHUTTER MOUNTING TYPE STILL STATES "WALL".PLEASE
 SPECIFY WHICH WALL CONNECTION YOU ARE USING FOR TOP AND
 BOTTOM.
  
 NEW COMMENT:
  
 2.)SEE SHEET 11.A 3" EDGE DISTANCE REQUIRES A
 FACTOR OF .83.
  