Text |
2008-02-22 09:36:34 | *** PROVISO *** |
| 1) PER 2004 FBC, FUEL GAS - POWERED EQUIPMENT |
| PERMANENTLY INSTALLED EQUIPMENT POWERED BY INTERNAL |
| COMBUSTION ENGINES SHALL BE INSTALLED IN ACCORDANCE |
| WITH MANUFACTURER'S INSTALLATION INSTRUCTIONS AND NFPA |
| 37.NFPA 37 INSTALLATION & USE OF STATIONARY |
| COMBUSTION ENGINES & GAS TURBINES: 4.1.4ENGINES |
| (GENERATORS) LOCATED OUTDOORS SHALL BE MINIMUM OF 5 FT |
| FROM OPENINGS IN WALLS & AT LEAST 5 FT FROM STRUCTURES |
| HAVING COMBUSTIBLE WALLS.A MINIMUM CLEARANCE IS NOT |
| REQUIRED WHEN (1) THE ADJACENT WALL HAS A MINIMUM FIRE |
| RESISTANCE RATING OF 1 HOUR OR (2) THE WEATHERPROOF |
| ENCLOSURE IS CONSTRUCTED OF NON-COMBUSTIBLE MATERIALS, |
| AND IT HAS BEEN DEMONSTRATED THAT A FIRE WITHIN THE |
| ENCLOSURE WILL NOT IGNITE COMBUSTIBLE |
| MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1 |
| EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES |
| OR |
| WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION |
| INTAKES. |
| 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS |
| LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE |
| TERMINATION POINT |
| SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF |
| STRUCTURE. |
| PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL |
| EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK, |
| GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED |
| CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E. |
| FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS. |
| FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES |
| AROUND EQUIPMENT FOR SERVICING,AND PROVIDE |
| MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE |
| FOR THE FIELD INSPECTOR. |
| |