Plan Review Notes
Plan Review Notes For Permit 07061034
Permit Number 07061034
Review Stop G
Sequence Number 2
Notes
Date Text
2008-01-29 11:01:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 NOTE: THE ORIGINAL GAS PERMIT APPLICATION FROM "A MAN
 SERVICE" PERMT #07061036 WAS NOT IN THE RESIDENTIAL
 GENERATOR PERMT #07061034 RESUBMITTAL, HOWEVER THERE
 WAS A GAS PERMIT APPLICATION SUBMITTED FROM "PALM BEACH
 GENERATOR" WITH NO PERMIT NUMBER ATTACHED. IF IT IS THE
 INTENT TO CHANGE CONTRACTORS OR VOID OUT THE ORIGINAL
 GAS PERMIT PLEASE CALL ADRIANNA MCKENZIE, OCCUPATIONAL
 LICENSE/PERMIT SUPERVISOR @ (561) 805-6681 TO ASSIST IN
 THIS PROCESS.
  
 THE FOLLOWING IS A PLAN REVIEW OF THE GAS PLANS
 SUBMITTED BY PALM BEACH GENERATOR:
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE SECTION *401.1 SCOPE.
 **NOT ALL CUT SECTIONS OF PIPE ARE INDICATING
 CORRESPONDING LENGTHS. PLEASE REFERENCE THE RED CIRCLED
 CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW. THE EXISTING
 GAS IS NOT BEING INDICATED, PLEASE SEE PERMIT
 INFORMATION INDICATING EXISTING GAS TO A TANKLESS WATER
 HEATER.
  
 2. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.**GALVANIZED
 PIPING UNDERGROUND IN NOT APPROVED. PER FBC FUEL GAS
 SECTION *404.8 PROTECTION AGAINST CORROSION.
  
 3. BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **THIS INCLUDES THE GAS TO THE EXISING TANKLESS WATER
 HEATER.
  
 4. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **THIS INCLUDES GAS TO THE EXISTING GAS TANLESS WATER
 HEATER.
  
 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NOTE: IF GAS SYSTEM DELIVERY PRESSURE NEEDS TO BE
 INCREASED TO 2 PSI WITH THE ADDITION OF THE EXISTING
 TANKLESS WATER HEATER PLEASE SUBMIT TWO COPIES OF THE
 MP REGULATORS INDICATING THE MAKE, MODEL NUMBER, BTU
 LOAD CAPACITY, AND A LISTING FROM A NATIONALLY
 RECOGNIZED TESTING LABORATORY.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]