2008-01-29 11:01:53 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| |
| GAS PLAN REVIEW: |
| DENIED 2ND TIME: |
| |
| NOTE: THE ORIGINAL GAS PERMIT APPLICATION FROM "A MAN |
| SERVICE" PERMT #07061036 WAS NOT IN THE RESIDENTIAL |
| GENERATOR PERMT #07061034 RESUBMITTAL, HOWEVER THERE |
| WAS A GAS PERMIT APPLICATION SUBMITTED FROM "PALM BEACH |
| GENERATOR" WITH NO PERMIT NUMBER ATTACHED. IF IT IS THE |
| INTENT TO CHANGE CONTRACTORS OR VOID OUT THE ORIGINAL |
| GAS PERMIT PLEASE CALL ADRIANNA MCKENZIE, OCCUPATIONAL |
| LICENSE/PERMIT SUPERVISOR @ (561) 805-6681 TO ASSIST IN |
| THIS PROCESS. |
| |
| THE FOLLOWING IS A PLAN REVIEW OF THE GAS PLANS |
| SUBMITTED BY PALM BEACH GENERATOR: |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE SECTION *401.1 SCOPE. |
| **NOT ALL CUT SECTIONS OF PIPE ARE INDICATING |
| CORRESPONDING LENGTHS. PLEASE REFERENCE THE RED CIRCLED |
| CUT SECTIONS THAT ARE HIGH LIGHTED YELLOW. THE EXISTING |
| GAS IS NOT BEING INDICATED, PLEASE SEE PERMIT |
| INFORMATION INDICATING EXISTING GAS TO A TANKLESS WATER |
| HEATER. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED.**GALVANIZED |
| PIPING UNDERGROUND IN NOT APPROVED. PER FBC FUEL GAS |
| SECTION *404.8 PROTECTION AGAINST CORROSION. |
| |
| 3. BTU LOAD OF EACH APPLIANCE AND THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33). |
| **THIS INCLUDES THE GAS TO THE EXISING TANKLESS WATER |
| HEATER. |
| |
| 4. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| **THIS INCLUDES GAS TO THE EXISTING GAS TANLESS WATER |
| HEATER. |
| |
| 5. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| **NOTE: IF GAS SYSTEM DELIVERY PRESSURE NEEDS TO BE |
| INCREASED TO 2 PSI WITH THE ADDITION OF THE EXISTING |
| TANKLESS WATER HEATER PLEASE SUBMIT TWO COPIES OF THE |
| MP REGULATORS INDICATING THE MAKE, MODEL NUMBER, BTU |
| LOAD CAPACITY, AND A LISTING FROM A NATIONALLY |
| RECOGNIZED TESTING LABORATORY. |
| |
| END OF COMMENTS: |
| |