Plan Review Notes
Plan Review Notes For Permit 07061034
Permit Number 07061034
Review Stop E
Sequence Number 1
Notes
Date Text
2007-07-16 13:53:04 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE
 PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE
 SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO
 RESUBMITTING.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC.
  
 3} PER 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY
 SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE
 SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE
 TIME. THE LOAD CALCULATION EXCEEDS THE GENERATOR
 OUTPUT.
  
 4} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE
 GENERATOR
 INDICATING RECOMMENDED SETBACKS FROM STRUCTURES.
  
 5} INDICATE WHICH TRANSFER SWITCH IS BEING USED. NOTE:
 GIVEN THE LOCATION IN THE SERVICE, THIS SWITCH MUST
 HAVE AN AIC RATING PER 110.9 AND 10.
  
 6} THE SPECIFICATIONS GIVEN FOR THE TRANSFER SWITCH
 INDICATES"UL RECOGNIZED DEVICE". PLEASE PROVIDE THE
 LISTING NUMBER OR HAVE THE MANUFACTURER VERIFY IN
 WRITING THE SWITCH HAS A UL 1008 LISTING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718