Plan Review Notes For Permit 07061034 |
Permit Number |
07061034 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-16 13:53:04 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE | | PLAN/DRAWINGS, SHALL PRINT AND SIGN THEIR NAME ON THE | | SHEETS THEY DRAW. PLEASE DO THIS PRIOR TO | | RESUBMITTING. | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3FBC. | | | | 3} PER 702.5 CAPACITY AND RATING. AN OPTIONAL STANDBY | | SYSTEM SHALL HAVE ADEQUATE CAPACITY AND RATING FOR THE | | SUPPLY OF ALL EQUIPMENT INTENDED TO BE OPERATED AT ONE | | TIME. THE LOAD CALCULATION EXCEEDS THE GENERATOR | | OUTPUT. | | | | 4} PROVIDE MANUFACTURERS SPECIFICATIONS FOR THE | | GENERATOR | | INDICATING RECOMMENDED SETBACKS FROM STRUCTURES. | | | | 5} INDICATE WHICH TRANSFER SWITCH IS BEING USED. NOTE: | | GIVEN THE LOCATION IN THE SERVICE, THIS SWITCH MUST | | HAVE AN AIC RATING PER 110.9 AND 10. | | | | 6} THE SPECIFICATIONS GIVEN FOR THE TRANSFER SWITCH | | INDICATES"UL RECOGNIZED DEVICE". PLEASE PROVIDE THE | | LISTING NUMBER OR HAVE THE MANUFACTURER VERIFY IN | | WRITING THE SWITCH HAS A UL 1008 LISTING. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW. | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|