Plan Review Notes
Plan Review Notes For Permit 07061023
Permit Number 07061023
Review Stop B
Sequence Number 2
Notes
Date Text
2007-07-05 15:57:32****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004
 EXISTING BUILDING CODE
 FBC*CITY OF WEST PALM BEACH
 AMENDMENTS TO THE FBC2004
  
 FROM PREVIOUS LIST:
  
 _XX_4.)FOR THE FLAT DECK, SELECT THE APPROVED
 ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER
 YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE
 LIMITATIONS.
  
 2ND REVIEW - THERE IS A NOTE WHICH STATES "SEE PAGES
 2,3,14,15".PLEASE CHOOSE AN ASSEMBLY.IT APPEARS
 THAT YOU MAY BE PROPOSING TO USE THE ASSEMBLY ON PAGES
 14-15, BUT ENHANCED FASTENING IS FOR BASE SHEET RATHER
 THAN INSULATION BOARD, AND PAGES 2 AND 3 ARE A LISTING
 OF PRODUCTS (NOT ASSEMBLIES).PLEASE MARK AN ASSEMBLY
 OR NOTE WHICH PAGE(S) THE ASSEMBLY IS ON, BUT REFER
 ONLY TO ONE OR TWO PAGES, ONE ASSEMBLLY ONLY.
  
 _XX_5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED
 FASTENING FOR CORNER AND PERIMETER ZONES.
  
 2ND REVIEW - THIS WAS WRITTEN ON TH EAPPLICATION AND ON
 THE CORRECTION LIST.THIS IS TO BE A PART OF YOUR
 PERMIT PACKAGE.PLEASE PROVIDE THE INFORMATION EITHER
 ON LETTERHEAD, A SEPARATE SHEET, OR WRITE IT DIRECTLY
 ON THE PRODUCT APPROVAL.TWO SETS OF ALL PERMIT
 DOCUMENTS ARE REQUIRED.ALSO, YOUR STATEMENT - "4 "
 O.C. PERIMETER4" O.C. " NOT ENTIRELY CLEAR, AND
 APPEARS TO BE FASTENING FOR A BASE SHEET, BUT YOU'VE
 SELECTED AN ASSEMBLY WITH INSULATION, SO ENHANCED
 FASTENING SHOULD STATE NUMBER OF FASTENERS PER BOARD.
 SEE RAS117.
  
  