2007-10-29 10:55:14 | DENIED 3RD TIME |
| REFERENCE: |
| ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| ** FLORIDA STATUTES (FS). |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE ON THE |
| RESUBMITTED DRAWINGS: |
| |
| 1. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE |
| RESUBMITTED PLANS NEED THE EXISTING BTU LOAD OF GAS |
| SYSTEM, AND THE PROPOSED BTU LOAD OF THE GENERATOR. PER |
| 106.1.2, ADDITIONAL INFORMATION REQUIRED. |
| |
| 2. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE |
| RESUBMITTED PLANS NEED THE LONGESTS LENGTH OF THE GAS |
| SYSTEM. (THIS INCLUDES THE EXISTING GAS SYSTEM) PER |
| 106.1.2, ADDITIONAL INFORMATION REQUIRED. |
| |
| 3. AS ASKED FOR ON PREVIOUS PLAN REVIEWS: THE |
| MANUFACTURER SPECIFICATION SHEETS FOR THE GENERATORS |
| 2ND STAGE REGULATOR NEED THE MANUFACTURER'S NAME (THIS |
| IS NOT INDICATED ON THE SUBMITTED DATA SHEETS), AND A |
| LISTING FROM A NATIONALLY RECOGNIZED TESTING LABORATORY |
| (THIS IS NOT INDICATED ON THE SUBMITTED DATA SHEETS) |
| PER 106.1.2, ADDITIONAL INFORMATION REQUIRED. |
| |
| 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY: MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL: [email protected] |
| |