Date |
Text |
2007-09-25 10:08:48 | DENIED 2ND TIME |
| REFERENCE: |
| ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL |
| IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS, |
| SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING |
| REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT |
| MADE ON PREVIOUS REVIEWS. |
| |
| ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM |
| PREVIOUS REVIEW WITH A NO, OK OR A NO/OK. |
| THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE |
| PREVIOUS REVIEW NOTES. |
| |
| A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR |
| FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS |
| ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER |
| EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT. |
| |
| AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL |
| COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS. |
| |
| A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN |
| ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW |
| COMMENT MAY HAVE BEEN FULLY ADDRESSED. |
| |
| ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF |
| THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH. |
| |
| 1. **NO** SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND |
| DOES NOT SHOW ALL CUT SECTIONSAND CORRESPONDING |
| LENGTHS TO THE PROPOSED GENERATOR. THE ONLY PIPING |
| INDICATED IS THE UNDERGROUND PE PIPE, THERE ARE NO |
| INDICATIONS OF THE ABOVE GROUND PIPING, 1ST AND 2ND |
| STAGE REGULATORS, SHUT OFF VALVES AND SEDIMENT TRAPS. |
| PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON |
| CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| |
| 2. **NO/OK** SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: REFERENCE COMMENT 1, WHERE ONLY THE UNDERGROUND |
| PIPING IS BEING INDICATED. |
| |
| 3. **OK** |
| |
| 4. **OK** |
| |
| 5. **OK** |
| |
| 6. **OK** |
| |
| 7. **NO** INDICATE THE DELIVERY PRESSURE ON THE |
| RESUBMITTAL, IF ITS LP GAS INDICATE 10 PSI. |
| |
| 8. **OK** |
| |
| 9. **NO** SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| NOTE: NEED MANUFACTURER SHEETS ON THE PROPOSED |
| GENERATOR VERIFYING THE BTU LOAD AND MANUFACTURER |
| SHEETS OF THE 2ND STAGE REGULATOR TO THE PROPOSED |
| GENERATOR INDICATING THE MAKE, MODEL NUMBER, LOAD |
| CAPACITY AND A LISTING FROM A NATIONALLY RECOGNIZED |
| TESTING LABORATORY. |
| |
| 10. **OK** |
| |
| 11. **OK** |
| |
| 12. **OK** |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |
| (561) 805-6730 |
| FAX (561) 805-6731 |