Review Stop G
Sequence Number 2
Notes
Date Text
2007-09-25 10:08:48DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 2006 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING ALONG WITH SOME NEW COMMENTS,
 SOME BASED ON PLANS NOW SUBMITTED, NEW DOCUMENTS BEING
 REVIEWED FOR THE FIRST TIME AND SOME NEW COMMENTS NOT
 MADE ON PREVIOUS REVIEWS.
  
 ** PLEASE SEE THE NOTES BELOW ARE TAKEN DIRECTLY FROM
 PREVIOUS REVIEW WITH A NO, OK OR A NO/OK.
 THESE WILL BE FOR THE EXACT NUMERICAL NOTATION OF THE
 PREVIOUS REVIEW NOTES.
  
 A NO IS IF THE COMMENT WAS NOT FULLY ADDRESSED AND/OR
 FURTHER EXPLANATION OR CHANGES IN PLANS OR DOCUMENTS
 ARE STILL NEEDED. THIS REVIEWER WILL TRY TO BETTER
 EXPLAIN NOTE ABOVE PREVIOUS REVIEW COMMENT.
  
 AN OK WILL BE LABELED AS SUCH ON THE SAME NUMERICAL
 COMMENT AND WILL HAVE OLD NOTE REMOVED FROM COMMENTS.
  
 A NO/OK MEANS PART OF THE COMMENT MAY HAVE BEEN
 ADDRESSED, HOWEVER NOT ALL OF THE PREVIOUS REVIEW
 COMMENT MAY HAVE BEEN FULLY ADDRESSED.
  
 ** PLEASE SEE ANY NEW NOTES WILL BE ADDED TO THE END OF
 THE PREVIOUS REVIEW COMMENTS AND NOTED AS SUCH.
  
 1. **NO** SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 NOTE: THE RESUBMITTED DRAWING IS NOT AN ISOMETRIC AND
 DOES NOT SHOW ALL CUT SECTIONSAND CORRESPONDING
 LENGTHS TO THE PROPOSED GENERATOR. THE ONLY PIPING
 INDICATED IS THE UNDERGROUND PE PIPE, THERE ARE NO
 INDICATIONS OF THE ABOVE GROUND PIPING, 1ST AND 2ND
 STAGE REGULATORS, SHUT OFF VALVES AND SEDIMENT TRAPS.
 PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. **NO/OK** SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
 NOTE: REFERENCE COMMENT 1, WHERE ONLY THE UNDERGROUND
 PIPING IS BEING INDICATED.
  
 3. **OK**
  
 4. **OK**
  
 5. **OK**
  
 6. **OK**
  
 7. **NO** INDICATE THE DELIVERY PRESSURE ON THE
 RESUBMITTAL, IF ITS LP GAS INDICATE 10 PSI.
  
 8. **OK**
  
 9. **NO** SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 NOTE: NEED MANUFACTURER SHEETS ON THE PROPOSED
 GENERATOR VERIFYING THE BTU LOAD AND MANUFACTURER
 SHEETS OF THE 2ND STAGE REGULATOR TO THE PROPOSED
 GENERATOR INDICATING THE MAKE, MODEL NUMBER, LOAD
 CAPACITY AND A LISTING FROM A NATIONALLY RECOGNIZED
 TESTING LABORATORY.
  
 10. **OK**
  
 11. **OK**
  
 12. **OK**
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730