Plan Review Notes For Permit 07061019 |
Permit Number |
07061019 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-16 08:07:25 | | | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE VALUE ON THE APPLICATION MUST | | INCLUDE THE TOTAL COST OF LABOR AND | | MATERIAL FOR THE GENERATOR, EQUIPMENT | | (TRANSFER SWITCHES, PANELS ETC.) | | AND PAD PER 108.3 FBC AS AMENDED. | | INCREASE THE VALUE AT THE COUNTER WHEN RESUBMITTING, | | AND GET A RECEIPT FROM THE | | PERMIT CLERK. | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | INDICATING RECOMMENDED SETBACKS AND | | ELECTRICAL SPEC'S FOR THE GENERATOR AND | | TRANSFER SWITCH. | | | | 3} PROVIDE A RISER DIAGRAM PER 215.5 | | INCLUDING GENERATOR AND RELATED | | EQUIPMENT. THE METER IS NOT SHOWN ON THE PLAN | | | | 4} PLEASE NOTE A DISCONNECT IS REQUIRED | | PER 225.31 AND 32. INDICATE LOCATION ON | | THE RISER AND SITE PLAN. THE TRANSFER | | SWITCH MAY NOT MEET THIS REQUIREMENT, | | SEE SPECS BEFORE SUBMITTING. | | | | 5} PROVIDE A LOAD CALCULATION FOR THE | | LOAD INTENDED TO BE SERVED. 215.5.PER ARTICLE 220 PART | | III, STANDARD OR PART IV OPTIONAL, INDICATE METHOD | | USED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] |
|