2007-07-30 13:32:39****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)AN 85" SPAN IS 7'1", SO YOU MUST USE THE 8' CHART,
 NOT THE 7' CHART.OPENING 1, CONNECTION E (BOTTOM),
 REQUIRES 7.5" SPACING.CHECK ALL OPENINGS.THE SPAN
 MAY BE OVERSTATED; CHECK WITH YOUR MANUFACTURER.THIS
 SHOULD BE THE BLADE LENGTH.