2007-07-18 11:58:20 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. CLEARLY SHOW THE LOCATION AND CAP- |
| ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| OR ASME), THE DISTANCE OF THE TANK FROM |
| THE BUILDING AND ADJACENT PROPERTY LINES |
| THE DISTANCE OF THE TANK FROM ALL SOUR- |
| CES OF IGNITION, OTHER CONTAINERS, BUILD |
| INGS, AND THE LOCATION OF ANY BUILDING |
| OPENINGS BELOW THE RELIEF VALVE OF THE |
| TANK PER NFPA 58, TABLE 3-2.2.2. |
| NOTE: PLEASE INDICATE THE DIMENSIONS OF LP TANK FROM |
| PROPERTY LINES AND STRUCTURES ON THE RESUBMITTAL. |
| |
| 2. CLEARLY INDICATE ON THE PLAN IF THE |
| LP TANK IS ABOVE OR BELOW GROUND, AND |
| SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| PER NFPA 58. IF THE TANK |
| IS BELOW GROUND THE CONTAINER SHALL BE |
| SECURILY ANCHORED PER NFPA 58 SECTION |
| 6.6.1. |
| NOTE: DETAIL OF TANK ANCHORING REQUIRED FOR THE |
| RESUBMITTAL. |
| |
| 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH |
| STANDARDS NFPA 54, NFPA 58, AND THE |
| FBC-2004 FUEL GAS CODE SEC 402.2. |
| NOTE: A} PLEASE CLEARLY INDICATE WHICH 1ST AND 2ND |
| STAGE REGULATOR IS BEING UESED ON THE RESUBMITTAL. THE |
| SUBMITTED REGULATOR SHEET IS INDICATING NINE (9) |
| REGULATORS. PLEASE INDICATE THAT THE REGULATORS BEING |
| USED SHOW A LISTING FROM A NATIONALLY RECOGNIZED |
| TESTING LABORATORY (NRTL) ON THE RESUBMITTAL. |
| B} PROVIDE MANUFACTURER'S SPECIFICATIONS FOR GENERATOR |
| INDICATING RECOMMENDED SETBACKS TO STRUCTURES. |
| |
| 4. FBC-2004 CHAPTER 1,SECTION 106.3.4.3: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING (GAS ISOMETRIC) SHALL CLEARLY PRINT AND |
| SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| END OF COMMENTS: |
| |