Plan Review Notes For Permit 07060981 |
Permit Number |
07060981 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-16 12:52:02 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING | | RECOMMENDED SETBACKS AND | | ELECTRICAL SPEC'S FOR THE | | TRANSFER SWITCH. | | | | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, | | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT | | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. | | DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3 | | FBC. | | | | 3} PROVIDE A PANEL SCHEDULE FOR THE | | GENERATOR PANEL. 106.3.5.4 FBC AS | | AMENDED. | | | | 4}PROVIDE A LOAD CALCULATION FOR THE | | LOAD INTENDED TO BE SERVED. 215.5. SEE PREVIOUS | | COMMENT | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | | | | | | | |
|