2007-07-16 12:52:02 
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1}PROVIDE MANUFACTURERS SPECIFICATIONS INDICATING
 RECOMMENDED SETBACKS AND
 ELECTRICAL SPEC'S FOR THE
 TRANSFER SWITCH.
  
 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
 DO THIS ON A SITE PLAN, NOT ON THE SURVEY, 106.1.3
 FBC.
  
 3} PROVIDE A PANEL SCHEDULE FOR THE
 GENERATOR PANEL. 106.3.5.4 FBC AS
 AMENDED.
  
 4}PROVIDE A LOAD CALCULATION FOR THE
 LOAD INTENDED TO BE SERVED. 215.5. SEE PREVIOUS
 COMMENT
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  