Plan Review Notes
Plan Review Notes For Permit 07060950
Permit Number 07060950
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-07-23 16:29:50*****DENIED*****
  
  
 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO
 BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS
 CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101,
 2003 EDITION, 7.2.1.6.2 ARE MET.PLEASE EXPLAIN (AS
 PER THE PLAN NOTES): STRIKES THAT ARE NOT FREE EGRESS
 DOORS MUST REMAIN IN THE LOCK DOWN MODE.
  
 2.THE NUMBER OF DOOR HARDWARE APPLIANCES ACTUALLY
 SEEN ON THE PLAN DOES NOT CORRELATE WITH WHAT IS
 DESCRIBED ON THE APPLICATION.
  
 3.IS THIS FLOOR AND (OR) TENANT SPACE A CHANGEFROM
 THAT OF A BUSINESS OCCUPANCY TO THAT OF A NEW DETENTION
 AND CORECTIONAL OCCUPANCY?
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722