Plan Review Notes For Permit 07060950 |
Permit Number |
07060950 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-23 16:29:50 | *****DENIED***** | | | | | | 1.DOORS IN THE MEANS OF EGRESS SHALL BE PERMITTED TO | | BE EQUIPPED WITH AN APPROVED ENTRANCE AND EGRESS ACCESS | | CONTROL SYSTEM PROVIDED THAT THE CRITERIA OF NFPA 101, | | 2003 EDITION, 7.2.1.6.2 ARE MET.PLEASE EXPLAIN (AS | | PER THE PLAN NOTES): STRIKES THAT ARE NOT FREE EGRESS | | DOORS MUST REMAIN IN THE LOCK DOWN MODE. | | | | 2.THE NUMBER OF DOOR HARDWARE APPLIANCES ACTUALLY | | SEEN ON THE PLAN DOES NOT CORRELATE WITH WHAT IS | | DESCRIBED ON THE APPLICATION. | | | | 3.IS THIS FLOOR AND (OR) TENANT SPACE A CHANGEFROM | | THAT OF A BUSINESS OCCUPANCY TO THAT OF A NEW DETENTION | | AND CORECTIONAL OCCUPANCY? | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | FIRE PLAN REVIEW | | 561-805-6722 |
|