Plan Review Notes
Plan Review Notes For Permit 07060932
Permit Number 07060932
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-08 20:11:58PROJECT: 736 FLAMINGO DRIVE
  
 PROJECT DETAIL: INSTALL 14 AWNINGS/NON-IMPACT
  
 PLAN REVIEW: 2004 FLORIDA BUILDING CODE W/ 2006
 REVISIONS
  
  
 STATUS: FAILED
  
 COMMENTS:
  
 1)PLEASE SHOW THAT THE AWNING STRUCTURAL FRAMING
 MEETS THE APPLICABLE WIND LOADS BASED ON RATIONAL
 ANALYSIS:
  
 3105.4.2
 DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL BE BASED
 ON RATIONAL ANALYSIS, USING THE APPLICABLE WIND LOADS
 OF CHAPTER 16 AS SHOWN BELOW:
  
 3105.4.2.1
 THE WIND DESIGN LOADS FOR ANY FABRIC OR
 MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK
 REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND
 VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING
 CRITERIA:
 1. MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90 MPH
 2. IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN LIFE
 OF 0.77.
 3. EXPOSURE CATEGORY B FOR OR C AS DEFINED IN CHAPTER
 16.
  
 2) PLEASE SUBMIT PHOTOGRAPHS INDICATING HOW THE FABRIC
 WILL BE QUICK RELEASED FROM THE FRAMING.
  
 3) STRUCTURES SHALL BE LABELED AS FOLLOWS:
  
 3105.5.3
 STRUCTURES DESIGNED TO BE READILY REMOVED OR
 REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY SHALL
 BE POSTED WITH A LEGIBLE AND READILY VISIBLE DECAL OR
 PAINTED INSTRUCTIONS TO THE OWNEROR TENANT
 TO REMOVE OR REPOSITION THE STRUCTURE OR PART THEREOF
 DURING SUCH PERIODS OF TIME AS ARE DESIGNATED BY THE
 U.S. WEATHER BUREAU AS BEING A HURRICANE WARNING OR
 ALERT.
  
 4) PLEASE SHOW CONNECTION DETAIL OF CAMEL BACK TO
 MAINFRAME OF EXISTING STRUCTURE:
  
 A) ANCHOR TYPE, DIAMETER, AND LENGTH.
 B) MINIMUM ANCHOR EMBEDMENT INTO MASONRY/WOOD
 STRUCTURE.
  
 5) SATISFY PLANING AND ZONING REQUIREMENTS.
  
  
 PLAN REVIEW: KEN CONRAD
 PHONE: 561.805.6666
  