2007-08-08 20:11:58 | PROJECT: 736 FLAMINGO DRIVE |
| |
| PROJECT DETAIL: INSTALL 14 AWNINGS/NON-IMPACT |
| |
| PLAN REVIEW: 2004 FLORIDA BUILDING CODE W/ 2006 |
| REVISIONS |
| |
| |
| STATUS: FAILED |
| |
| COMMENTS: |
| |
| 1)PLEASE SHOW THAT THE AWNING STRUCTURAL FRAMING |
| MEETS THE APPLICABLE WIND LOADS BASED ON RATIONAL |
| ANALYSIS: |
| |
| 3105.4.2 |
| DESIGN OF THE STRUCTURAL FRAMING MEMBERS SHALL BE BASED |
| ON RATIONAL ANALYSIS, USING THE APPLICABLE WIND LOADS |
| OF CHAPTER 16 AS SHOWN BELOW: |
| |
| 3105.4.2.1 |
| THE WIND DESIGN LOADS FOR ANY FABRIC OR |
| MEMBRANE-COVERED STRUCTURE DESIGNED WITH A QUICK |
| REMOVAL OR BREAKAWAY MEMBRANE OR FABRIC AT WIND |
| VELOCITIES OF 75 MPH, SHALL BE BASED ON THE FOLLOWING |
| CRITERIA: |
| 1. MINIMUM WIND VELOCITY OF 3-SECOND WIND GUST 90 MPH |
| 2. IMPORTANCE FACTOR BASED ON LOW HAZARD TO HUMAN LIFE |
| OF 0.77. |
| 3. EXPOSURE CATEGORY B FOR OR C AS DEFINED IN CHAPTER |
| 16. |
| |
| 2) PLEASE SUBMIT PHOTOGRAPHS INDICATING HOW THE FABRIC |
| WILL BE QUICK RELEASED FROM THE FRAMING. |
| |
| 3) STRUCTURES SHALL BE LABELED AS FOLLOWS: |
| |
| 3105.5.3 |
| STRUCTURES DESIGNED TO BE READILY REMOVED OR |
| REPOSITIONED DURING PERIODS OF HIGH WIND VELOCITY SHALL |
| BE POSTED WITH A LEGIBLE AND READILY VISIBLE DECAL OR |
| PAINTED INSTRUCTIONS TO THE OWNEROR TENANT |
| TO REMOVE OR REPOSITION THE STRUCTURE OR PART THEREOF |
| DURING SUCH PERIODS OF TIME AS ARE DESIGNATED BY THE |
| U.S. WEATHER BUREAU AS BEING A HURRICANE WARNING OR |
| ALERT. |
| |
| 4) PLEASE SHOW CONNECTION DETAIL OF CAMEL BACK TO |
| MAINFRAME OF EXISTING STRUCTURE: |
| |
| A) ANCHOR TYPE, DIAMETER, AND LENGTH. |
| B) MINIMUM ANCHOR EMBEDMENT INTO MASONRY/WOOD |
| STRUCTURE. |
| |
| 5) SATISFY PLANING AND ZONING REQUIREMENTS. |
| |
| |
| PLAN REVIEW: KEN CONRAD |
| PHONE: 561.805.6666 |
| |