2007-07-13 14:35:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)SEE OPENING 19.OPENINGS OVER 104" (8'8") REQUIRE
 USE OF THE NEXT CHART.9" SPACING REQUIRED FOR C2
 CONNECTION.CHECK ALL CONNECTIONS.
  
 2.)PLEASE EXPLAIN HOW AN OUTSIDE MOUNT WITH A 3" EDGE
 DISTANCE TOP AND BOTTOM CAN HAVE A SPAN WHICH IS THE
 SAME AS THE OPENING.PLEASE PROVIDE A SKETCH OR ADVISE
 AS TO WHERE THIS CAN BE FOUND ON THE PRODUCT APPROVAL.
  
 3.)YOU HAVE CIRCLED DETAILS ON THE HR AND 6.8 PAGES.
 WHICH PRODUCT ARE YOU USING?ONLY DETAILS APPLICABLE
 TO THIS JOB SHOULD BE CIRCLED.
  