2007-10-02 16:31:42 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC |
| FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| FROM PREVIOUS LIST: |
| |
| 1.)THE FIRST COMMENT LIST REQUESTED THAT YOU SHOW HOW |
| EGRESS IS AFFECTED.YOU ARE BLOCKING THREE DOORS, |
| INCLUDING THE MAIN ENTRY DOOR.YOU CANNOT BLOCK A |
| REQUIRED MEANS OF EGRESS WITH HURRICANE SHUTTERS. |
| PLEASE SEE FBC CHAPTER 10, PARTICULARLY FBC1001.4 |
| (CANNOT REDUCE THE REQUIRED MEANS OF EGRESS), FBC1007.1 |
| AND FBC11, FBC1008 (DOORS).PROVIDE A LIFE SAFETY PLAN |
| INCLUDING FLOOR PLAN, PATH OF TRAVEL, OCCUPANCY |
| CLASSIFICATION FBC3, OCCUPANT LOAD FBC10.YOU CANNOT |
| BLOCK THE MAIN ENTRANCE.IT IS NOT CLEAR IF THE OTHER |
| TWO DOORS ARE REQUIRED MEANS OF EGRESS OR ACCESSIBLE |
| MEANS OF EGRESS.PROVIDE PLANS WHICH SHOW CODE |
| COMPLIANCE, TO BE PREPARED BY A DESIGN PROFESSIONAL. |
| |
| COMMENT NOT ADDRESSED.SEE THE FOLLOWING CODES, ALL |
| WHICH PROHIBIT BLOCKING THE REQUIRED EXITS:FBC1001.2 |
| (UNLAWFUL TO ALTER A BUILDING THAT WILL REDUCE THE |
| NUMBER OF EXITS OR THE CAPACITY OF THE MEANS OF EGRESS |
| TO LESS THAN REQUIRED), FBC1003.6 (PATH OF EGRESS |
| TRAVEL SHALL NOT BE INTERRUPTED BY ANY BUILDING ELEMENT |
| OTHER THAN A MEANS OF EGRESS COMPONENT).SOMEONE WROTE |
| "EGRESS IS PROVIDED BY SHUTTERS THAT CAN BE DEPLOYED |
| AND REMOVED FROM THE NSIDE OR OUTSIDE."THERE IS |
| PROVISION FOR THIS IN RESIDENTIAL CODE, BUT NOT IN |
| FLORIDA BUILDING CODE.IF YOU FEEL THAT I AM |
| INCORRECT, PROVIDE THE CODE SECTION WHICH ALLOWS THIS. |
| |
| |
| DO NOT RESUBMIT WITHOUT THE REQUIRED LIFE SAFETY PLAN |
| SHOWING ALL REQUIRED EXIT DOORS UNLESS YOUR SHUTTER |
| PLAN IS TO INCLUDE WINDOWS ONLY. |
| |
| |