Plan Review Notes For Permit 07060909
Permit Number 07060909
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-13 15:53:22****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE SPANS SHOULD BE 3" LARGER THAN THE OPENING
 (IF THERE IS A 3" EDGE DISTANCE).OPENINGS 4 AND 5 ARE
 OVER 8'8", REQUIRING 9" ANCHOR SPACING FOR THE C2
 CONNECTION RATHER THAN 12".
  
 2.)DETAILS FOR THE HR SHUTTER ARE CIRCLED.PLEASE
 CIRCLE ONLY DETAILS SPECIFIC TO THIS JOB.THESE SHEETS
 (9-13) MAY BE REMOVED UNLESS YOU ARE USING THE HR, IN
 WHICH CASE THE INSTALLATION SCHEDULE SHOULD BE
 REVISED.