Plan Review Notes For Permit 07060847 |
Permit Number |
07060847 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-17 08:19:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | CODE | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | FAC FLORIDA ADMINISTRATIVE CODE | | FSFLORIDA STATUTE | | | | | | 1.)INCLUDE A CODE SUMMARY; BUILDING TYPE FBC6, | | BUILDING HEIGHT AND AREA FBC5, SPRINKLER INFORMATION | | OCCUPANCY CLASSIFICATINO FBC 3 AND AREA PER OCCUPANCY. | | THIS REQUEST IS TO CLARIFY USE OF COMBUSTIBLES IN THE | | ROOF FRAMING. | | | | 2.)PROVIDE PRODUCT APPROVALS FOR THE ROOF.PRODUCT | | APPROVALS ARE TO BE APPROVED BY DESIGNER OFV RECORD | | (SHOP DRAWING REVIEW STAMP OR LETTER), FBC*106.3.3. |
|