Plan Review Notes
Plan Review Notes For Permit 07060823
Permit Number 07060823
Review Stop E
Sequence Number 7
Notes
Date Text
2008-08-08 10:00:43**DENIEDREVIEW**
  
  
  
 1) NOTE:PLEASE SEE THAT PLANS WERE SUBMITTED FOR
 *RE-STAMP ONLY* FOR INSPECTIONS YET THERE ARE REVISIONS
 NOW HAND DRAWN ON PAGES.
 PLANS NOW SHOW ELECTRICAL PANEL IN TWO LOCATIONS.
 PLANS NOW SHOW METER IN TWO LOCATIONS.
  
 ** IF PLANS ARE BEING REVISED PLEASE HAVE THE DESIGNER
 OF RECORD REVISE PLANS, REPRINT SHEETS WITH OUT HAND
 DRAWN CHANGES AND SUBMIT AS REVISIONS NOT AS A
 RE-STAMP.
 A RE-STAMP IS ONLY FOR PLANS WHICH ARE *EXACTLY* AS
 ALREADY ON FILE WITH NO CHANGES.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]