Plan Review Notes
Plan Review Notes For Permit 07060823
Permit Number 07060823
Review Stop E
Sequence Number 4
Notes
Date Text
2007-11-02 12:11:26 
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS
 INCLUDING NEW COMMENTS ARE STILL NEEDED TO BE
 ADDRESSED.
  
  
 1) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE
 DINING ROOM RECEPTACLES SHALL BE ON ONE OR MORE OF THE
 SMALL APPLIANCE CIRCUITS. IF MORE THAN THE TWO MINIMUM
 THEN PLEASE SEE THE ADDITIONAL VA IS 1500 VA FOR EACH.
 PANEL AND LOAD ONLY SHOWS 1.0 KVA.
  
  
 2) NOTE: PLEASE SEE THE PANEL SCHEDULE HAS NOW CHANGED
 THE AHU HEAT DOWN TO 5KW WHEN THE PREVIOUS HAD THE HEAT
 AS 10KW. THE PREVIOUS REVIEW GAVE A NOTICE TO 424.3B AS
 THE CIRCUIT WAS A SINGLE POLE 20AMP CIRCUIT. THERE WAS
 NO COMMENT ABOUT THE KW RATING TO BE CHANGED. PLEASE
 SEE THE LOAD CALCULATIONS STILL CONTAIN 10KW WHEN PANEL
 IS 5KW.
 PLEASE COORDINATE AND ADJUST. FBC 106.3.5.4, 106.1.2,
 NEC 310.16, 240.4 ETC
 ** PLEASE SEE THE OVER CURRENT PROTECTION AND CIRCUIT
 SIZE FOR THE 3-TON CONDENSING UNIT IS TOO HIGH. PLEASE
 KNOW THE MAXIMUM OVER CURRENT PROTECTION IS STATED IN
 THE NEC AND BY THE MANUFACTURE.
 110.3, 90.7, 422.11E(3)
  
 3) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO
 THE OWNER BUILDER APPLYING FOR AN OWNER BUILDER PERMIT
 WHEN HOMESTEAD EXEMPTION IS LISTED ON MULTIPLE
 PROPERTIES. THIS WILL BE VERIFIED WITH THE BUILDING
 OFFICIAL AND LAW DEPARTMENT. CONTACT MAY BE MADE TO THE
 PROPERTY APPRAISER'S OFFICE TO VERIFY THE ALLOWANCE AS
 STATED IN FS 489.
  
 4) NOTE: PLEASE SEE THE SMOKE ALARMS ARE NOT CIRCUITED
 SO THE VERIFICATION OF THE REQUIRED ARC FAULT
 PROTECTION PER 210.12.
  
 5) NOTE: PLEASE SEE CODE AS LISTED FOR BATH CIRCUIT
 DOES NOT NEED TO BE ON PLANS. THIS IS SHOWN AS
 210.11-2-3, HOWEVER THE CORRECT CODE IS 210.11C3. THIS
 WOULD HAVE BEEN REDLINED IF THIS WAS THE ONLY ITEM.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717