2007-11-02 12:11:26 | |
| ** DENIED 3RD REVIEW ** |
| |
| ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS |
| INCLUDING NEW COMMENTS ARE STILL NEEDED TO BE |
| ADDRESSED. |
| |
| |
| 1) NOTE: PLEASE SEE 210.52B1, 210.11C1, 220.53 AS THE |
| DINING ROOM RECEPTACLES SHALL BE ON ONE OR MORE OF THE |
| SMALL APPLIANCE CIRCUITS. IF MORE THAN THE TWO MINIMUM |
| THEN PLEASE SEE THE ADDITIONAL VA IS 1500 VA FOR EACH. |
| PANEL AND LOAD ONLY SHOWS 1.0 KVA. |
| |
| |
| 2) NOTE: PLEASE SEE THE PANEL SCHEDULE HAS NOW CHANGED |
| THE AHU HEAT DOWN TO 5KW WHEN THE PREVIOUS HAD THE HEAT |
| AS 10KW. THE PREVIOUS REVIEW GAVE A NOTICE TO 424.3B AS |
| THE CIRCUIT WAS A SINGLE POLE 20AMP CIRCUIT. THERE WAS |
| NO COMMENT ABOUT THE KW RATING TO BE CHANGED. PLEASE |
| SEE THE LOAD CALCULATIONS STILL CONTAIN 10KW WHEN PANEL |
| IS 5KW. |
| PLEASE COORDINATE AND ADJUST. FBC 106.3.5.4, 106.1.2, |
| NEC 310.16, 240.4 ETC |
| ** PLEASE SEE THE OVER CURRENT PROTECTION AND CIRCUIT |
| SIZE FOR THE 3-TON CONDENSING UNIT IS TOO HIGH. PLEASE |
| KNOW THE MAXIMUM OVER CURRENT PROTECTION IS STATED IN |
| THE NEC AND BY THE MANUFACTURE. |
| 110.3, 90.7, 422.11E(3) |
| |
| 3) NOTE: PLEASE SEE PREVIOUS COMMENT WITH RESPECT TO |
| THE OWNER BUILDER APPLYING FOR AN OWNER BUILDER PERMIT |
| WHEN HOMESTEAD EXEMPTION IS LISTED ON MULTIPLE |
| PROPERTIES. THIS WILL BE VERIFIED WITH THE BUILDING |
| OFFICIAL AND LAW DEPARTMENT. CONTACT MAY BE MADE TO THE |
| PROPERTY APPRAISER'S OFFICE TO VERIFY THE ALLOWANCE AS |
| STATED IN FS 489. |
| |
| 4) NOTE: PLEASE SEE THE SMOKE ALARMS ARE NOT CIRCUITED |
| SO THE VERIFICATION OF THE REQUIRED ARC FAULT |
| PROTECTION PER 210.12. |
| |
| 5) NOTE: PLEASE SEE CODE AS LISTED FOR BATH CIRCUIT |
| DOES NOT NEED TO BE ON PLANS. THIS IS SHOWN AS |
| 210.11-2-3, HOWEVER THE CORRECT CODE IS 210.11C3. THIS |
| WOULD HAVE BEEN REDLINED IF THIS WAS THE ONLY ITEM. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| SHOULD BE SUBMITTED FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| DELAYS. |
| |