Plan Review Notes For Permit 07060823 |
Permit Number |
07060823 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-11-02 14:18:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST | | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | (F.S.). | | | | *** DENIED *** | | 1) ONLY ONE COPY OF THE ENERGY CALCULATIONS AND COOLING | | LOAD CALCULATION WERE SUBMITTED, TWO COPIES NEED TO BE | | SUBMITTED, SEE 2004 WPB AMEND. 106.1. | | | | 2) COOLING LOAD CALCULATIONS ARE CALLING FOR 25,286 | | TOTAL BTU'S. MECHANICAL PLAN IS CALLING FOR 35,000 | | TOTAL BTU'S. THE MECHANICAL PLANS CAN ONLY CALL FOR 15% | | MORE THAN THE COOLING LOAD CALCULATIONS, SEE 2004 FBC | | 13-607.1.ABC.1.1. PLEASE CORRECT. | | | | 3) MECHANICAL PLAN IS CALLING FOR A 8 KW HEATER, | | ELECTRICAL PLAN IS CALLING FOR A 5 KW IN ONE PLACE AND | | A 10 KW IN ANOTHER PLACE, THE THREE MUST COINCIDE, | | PLEASE CORRECT. | | | | 4) THE MECHANICAL PLANS NEED THESIGNATURE OF THE | | PERSON RESPONSIBLE FOR THE DESIGN ON THEM, SEE W.P.B. | | AMEND. 106.1.3. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729 | | E-MAIL; [email protected] | | |
|