Date |
Text |
2007-08-27 18:05:55 | |
| *** DENIED 2ND REVIEW *** |
| |
| ** PLEASE SEE THERE ARE STILL SOME COMMENTS FROM THE |
| PREVIOUS REVIEW WHICH NEED TO BE ADDRESSED ALONG WITH |
| SOME NEW COMMENTS BASED ON REVISIONS MADE TO PLANS AND |
| INFORMATION WHICH COULD NOT BE REVIEWED PREVIOUSLY. |
| |
| |
| 1) NOTE:AS STATED ON THE PREVIOUS REVIEW:PLEASE SEE |
| THE PERMIT IS BEING APPLIED AS OWNER/ BUILDER WHERE THE |
| PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE ALREADY |
| LIST THIS OWNER NOT ONLY ON SEVERAL OTHER PROPERTIES |
| BUT ALSO WITH HOMESTEAD EXEMPTION LISTED ON MORE THEN |
| ONE PROPERTY WHICH IS NOT PERMITTED UNDER FLORIDA LAW. |
| PLEASE SEE THIS INFORMATION FOR MULTIPLE HOMESTEADS |
| WILL BE FORWARDED TO THE PBCPA OFFICE. |
| PLEASE SEE THAT IN ORDER TO PULL AN OWNER/BUILDER |
| PERMIT YOU MUST MEET THE EXCEPTION UNDER FS 489. PLEASE |
| KNOW THIS MAY AFFECT THE PERMIT AS APPLIED AND A |
| CONTRACTOR MAY BE REQUIRED. INFORMATION MAY ALSO BE |
| FORWARDED TO THE COUNTY AND STATE LICENSING BOARD FOR |
| REVIEW. |
| |
| 2) NOTE: PLEASESTILL CLARIFY THE MAINPANEL. THE |
| PANEL DESCRIPTION STATES THE PANEL IS A NEMA 3R WHICH |
| IS AN OUTDOOR PANEL, YET THE PLANS SHOW THIS PANEL |
| INSIDE? |
| PLEASE KNOW THAT QUOTING THE CODE ON PLANS IN LIEU OF |
| SPECIFIC DETAIL IS NOT PERMITTED. |
| 230.70,230.71. |
| |
| 3) NOTE: AS PREVIOUSLY NOTED: |
| PLEASE INDICATE THE AIC RATINGS ON NEW RISER AS THE |
| NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE ONCE THE |
| RISER IS REVISED. 110.9 |
| |
| 4) NOTE: AS PREVIOUSLY NOTED: |
| PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS THE LOADS |
| FOR ALL SMALL APPLIANCE AND DINING ROOM CIRCUITS SHALL |
| BE FIGURED INTO THE LOAD CALCULATIONS. PLEASE CLARIFY |
| THE DINING ROOM/AREA. |
| PLEASE SEE THE PLANS INDICATE 15AMP CIRCUIT FOR DINING |
| WHICH IS NOT PERMITTED. |
| PLEASE SEE THE PLANS INDICATE A SWITCHED RECEPTACLE IN |
| THE DINING AREA ON THE LIGHTING CIRCUIT WHICH IS ALSO |
| NOT PERMITTED. |
| PLEASE ALSO SEE THE PANEL SCHEDULE IS SHOWING 15AMP OCP |
| FOR THE SMALL APPLIANCE CIRCUITS WHICH IS NOT |
| PERMITTED. |
| PLEASE ADJUST THE LOAD CALCULATIONS. |
| PLEASE ADJUST THE CIRCUITS. |
| PLEASE ADJUST THE OVER CURRENT PROTECTION. |
| ETC. |
| |
| 5) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL |
| LOCATION AND IDENTIFY THE LOCATIONS OF THE CU |
| DISCONNECT PER 440.11. QUOTING THE CODE IN LIEU OF |
| SPECIFIC DESIGN OR DETAIL CAN NOT BE ACCEPTED. |
| FBC 106.1.3, 106.1, 106.3.5.4 |
| |
| 6) NOTE: PLEASE VERIFY THE GDO/ GARAGE DOOR OPENER ON |
| WITH THE OUTSIDE GFI RECEPTACLES. |
| THIS WILL NOT BE PERMITTED AS THE LOAD ON GD OPENERS |
| TYPICALLY IS LARGE ENOUGH ON THE HORSEPOWER RATING TO |
| REQUIRE A DEDICATED CIRCUIT. EVEN THOUGH THE OUTSIDE |
| GFI ARE GENERAL PURPOSE AND DO NOT CONTAIN ANY SPECIFIC |
| LOAD AT THIS TIME, THESE ARE USED FOR LANDSCAPE |
| LIGHTING, HOLIDAY LIGHTING, YARD EQUIPMENT ETC WHICH |
| WOULD OVER LOAD THIS CIRCUIT. |
| PLEASE ADJUST AND PROVIDE DEDICATE GDO CIRCUIT. |
| 430.248 |
| |
| 7) NOTE: PLEASE SHOW ALL ROOM AND AREA DESIGNATIONS ON |
| PLANS. PLEASE BE SURE TO SHOW ALL OF THE CIRCUITS AS |
| SOME ARE MISSING. |
| FBC 106.1.2 |
| |
| 8) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED |
| CIRCUITS ON PANEL SCHEDULE. |
| PLEASE SEE AS NO CIRCUIT IS SHOWN FOR THE SMOKE ALARMS, |
| NEED TO VERY AFCI PROTECTION. |
| PLEASE SEE THE PLANS ONLY SHOW AFCI PROTECTION FOR |
| RECEPTACLES. THIS CHANGED IN THE 2002 CODE TO REQUIRE |
| THE AFCI PROTECTION FOR ALL OUTLETS. AS REQUESTED IN |
| THE PREVIOUS REVIEW, PLEASE SHOW THE REQUIRED |
| PROTECTION FOR ALL REQUIRED CIRCUITS. |
| 210.12, 408.4 |
| |
| 9) NOTE: AS REQUESTED ON PREVIOUS REVIEW: |
| PLANS ARE STILL NOT SIGNED, DATED OR SEAL AS REQUIRED |
| BY A DESIGNER OF RECORD OR DESIGN PROFESSIONAL. FS |
| 481.229, 471.003, 489, ETC |
| PLEASE SEE THE TITLE BLOCK INDICATES HOMES DESIGNED BY |
| ETC HOWEVER NO LICENSE INFORMATION WAS STATED ON TILE |
| BLOCKS FOR SAID FIRM. FAC 61G1-16.004, 61G15-23.002, FS |
| 481.219 AND 471.023. |
| PLEASE SEE THE PLANS EVEN STATE * NOT VALID WITHOUT |
| SEAL*. |
| |
| 10) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT |
| PROTECTION REQUIRED FOR THE AHU> SHOWS 1-POLE 20AMP |
| BREAKER AND #10AWG?? YET PLANS INDICATE 10KW HEAT. |
| |
| 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE |
| COMPLIANCE AS SOME COMMENTS ARE REPEATED. |
| |
| |
| ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR |
| SUBMITTED FOR REVIEW, THE REVIEW FOR CODE COMPLIANCE |
| CAN ONLY BE BASED ON THE PLANS SUBMITTED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES |
| WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |