Plan Review Notes
Plan Review Notes For Permit 07060823
Permit Number 07060823
Review Stop E
Sequence Number 2
Notes
Date Text
2007-08-27 18:05:55 
 *** DENIED 2ND REVIEW ***
  
 ** PLEASE SEE THERE ARE STILL SOME COMMENTS FROM THE
 PREVIOUS REVIEW WHICH NEED TO BE ADDRESSED ALONG WITH
 SOME NEW COMMENTS BASED ON REVISIONS MADE TO PLANS AND
 INFORMATION WHICH COULD NOT BE REVIEWED PREVIOUSLY.
  
  
 1) NOTE:AS STATED ON THE PREVIOUS REVIEW:PLEASE SEE
 THE PERMIT IS BEING APPLIED AS OWNER/ BUILDER WHERE THE
 PALM BEACH COUNTY PROPERTY APPRAISER'S OFFICE ALREADY
 LIST THIS OWNER NOT ONLY ON SEVERAL OTHER PROPERTIES
 BUT ALSO WITH HOMESTEAD EXEMPTION LISTED ON MORE THEN
 ONE PROPERTY WHICH IS NOT PERMITTED UNDER FLORIDA LAW.
 PLEASE SEE THIS INFORMATION FOR MULTIPLE HOMESTEADS
 WILL BE FORWARDED TO THE PBCPA OFFICE.
 PLEASE SEE THAT IN ORDER TO PULL AN OWNER/BUILDER
 PERMIT YOU MUST MEET THE EXCEPTION UNDER FS 489. PLEASE
 KNOW THIS MAY AFFECT THE PERMIT AS APPLIED AND A
 CONTRACTOR MAY BE REQUIRED. INFORMATION MAY ALSO BE
 FORWARDED TO THE COUNTY AND STATE LICENSING BOARD FOR
 REVIEW.
  
 2) NOTE: PLEASESTILL CLARIFY THE MAINPANEL. THE
 PANEL DESCRIPTION STATES THE PANEL IS A NEMA 3R WHICH
 IS AN OUTDOOR PANEL, YET THE PLANS SHOW THIS PANEL
 INSIDE?
 PLEASE KNOW THAT QUOTING THE CODE ON PLANS IN LIEU OF
 SPECIFIC DETAIL IS NOT PERMITTED.
 230.70,230.71.
  
 3) NOTE: AS PREVIOUSLY NOTED:
 PLEASE INDICATE THE AIC RATINGS ON NEW RISER AS THE
 NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE ONCE THE
 RISER IS REVISED. 110.9
  
 4) NOTE: AS PREVIOUSLY NOTED:
 PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS THE LOADS
 FOR ALL SMALL APPLIANCE AND DINING ROOM CIRCUITS SHALL
 BE FIGURED INTO THE LOAD CALCULATIONS. PLEASE CLARIFY
 THE DINING ROOM/AREA.
 PLEASE SEE THE PLANS INDICATE 15AMP CIRCUIT FOR DINING
 WHICH IS NOT PERMITTED.
 PLEASE SEE THE PLANS INDICATE A SWITCHED RECEPTACLE IN
 THE DINING AREA ON THE LIGHTING CIRCUIT WHICH IS ALSO
 NOT PERMITTED.
 PLEASE ALSO SEE THE PANEL SCHEDULE IS SHOWING 15AMP OCP
 FOR THE SMALL APPLIANCE CIRCUITS WHICH IS NOT
 PERMITTED.
 PLEASE ADJUST THE LOAD CALCULATIONS.
 PLEASE ADJUST THE CIRCUITS.
 PLEASE ADJUST THE OVER CURRENT PROTECTION.
 ETC.
  
 5) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL
 LOCATION AND IDENTIFY THE LOCATIONS OF THE CU
 DISCONNECT PER 440.11. QUOTING THE CODE IN LIEU OF
 SPECIFIC DESIGN OR DETAIL CAN NOT BE ACCEPTED.
 FBC 106.1.3, 106.1, 106.3.5.4
  
 6) NOTE: PLEASE VERIFY THE GDO/ GARAGE DOOR OPENER ON
 WITH THE OUTSIDE GFI RECEPTACLES.
 THIS WILL NOT BE PERMITTED AS THE LOAD ON GD OPENERS
 TYPICALLY IS LARGE ENOUGH ON THE HORSEPOWER RATING TO
 REQUIRE A DEDICATED CIRCUIT. EVEN THOUGH THE OUTSIDE
 GFI ARE GENERAL PURPOSE AND DO NOT CONTAIN ANY SPECIFIC
 LOAD AT THIS TIME, THESE ARE USED FOR LANDSCAPE
 LIGHTING, HOLIDAY LIGHTING, YARD EQUIPMENT ETC WHICH
 WOULD OVER LOAD THIS CIRCUIT.
 PLEASE ADJUST AND PROVIDE DEDICATE GDO CIRCUIT.
 430.248
  
 7) NOTE: PLEASE SHOW ALL ROOM AND AREA DESIGNATIONS ON
 PLANS. PLEASE BE SURE TO SHOW ALL OF THE CIRCUITS AS
 SOME ARE MISSING.
 FBC 106.1.2
  
 8) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE.
 PLEASE SEE AS NO CIRCUIT IS SHOWN FOR THE SMOKE ALARMS,
 NEED TO VERY AFCI PROTECTION.
 PLEASE SEE THE PLANS ONLY SHOW AFCI PROTECTION FOR
 RECEPTACLES. THIS CHANGED IN THE 2002 CODE TO REQUIRE
 THE AFCI PROTECTION FOR ALL OUTLETS. AS REQUESTED IN
 THE PREVIOUS REVIEW, PLEASE SHOW THE REQUIRED
 PROTECTION FOR ALL REQUIRED CIRCUITS.
 210.12, 408.4
  
 9) NOTE: AS REQUESTED ON PREVIOUS REVIEW:
 PLANS ARE STILL NOT SIGNED, DATED OR SEAL AS REQUIRED
 BY A DESIGNER OF RECORD OR DESIGN PROFESSIONAL. FS
 481.229, 471.003, 489, ETC
 PLEASE SEE THE TITLE BLOCK INDICATES HOMES DESIGNED BY
 ETC HOWEVER NO LICENSE INFORMATION WAS STATED ON TILE
 BLOCKS FOR SAID FIRM. FAC 61G1-16.004, 61G15-23.002, FS
 481.219 AND 471.023.
 PLEASE SEE THE PLANS EVEN STATE * NOT VALID WITHOUT
 SEAL*.
  
 10) NOTE: PLEASE SEE 424.3B FOR MINIMUM OVER CURRENT
 PROTECTION REQUIRED FOR THE AHU> SHOWS 1-POLE 20AMP
 BREAKER AND #10AWG?? YET PLANS INDICATE 10KW HEAT.
  
 11) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 DESIGN PROFESSIONALS AND REPEAT COMMENTS FOR CODE
 COMPLIANCE AS SOME COMMENTS ARE REPEATED.
  
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR
 SUBMITTED FOR REVIEW, THE REVIEW FOR CODE COMPLIANCE
 CAN ONLY BE BASED ON THE PLANS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]