2007-09-25 16:57:592004 FBC W/2006 SUPPLEMENT
 NEW SINGLE FAMILY DWELLING
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 3) SUBMIT TWO COPIES OF THE ENERGY CALCULATIONS AND
 COMPLY WITH MECHANICAL REVIEW COMMENTS.
  
 4) SOME OF THE INFORMATION LISTED ON THE STORM PANEL
 SCHEDULE IS INCORRECT. THE GLASS SEPARATION IS REQUIRED
 TO BE A MINIMUM OF 2-3/4" PER TABLE 2 ON SHEET 6 OF THE
 NOA. THE SPAN IS THE LENGTH OF THE PANELS WHICH WILL BE
 WIDER THAN THE OPENING PLUS THE EDGE DISTANCE AT BOTH
 SIDES OF THE OPENING. FOR EXAMPLE IF THE SHUTTER IS
 INSTALLED VERTICALLY AND THE OPENING HEIGHT IS 63" WITH
 A 2" EDGE DISTANCE, THEN THE SPAN WOULD HAVE TO BE AT
 LEAST 67" FOR C TRACK INSTALLATION. PLEASE REVIEW THE
 NOA.
  