2007-06-28 14:15:24 | *** DENIED *** |
| 1) SEE ENERGY CALCULATIONS LINE 11A SHOWS 25 FT OF |
| SUPPLY AIR IN ATTIC, PLEASE RE-CHECK AS MECHANICAL |
| PLANS SHOW OVER 100 FT. OF SUPPLY AIR DUCT IN THE |
| ATTIC, CORRECT E-CAL'S. |
| |
| 2) ENERGY CALCULATIONS NEED TO BE SIGNED BY OWNER/AGENT |
| ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| |
| 3) ENERGY CALCULATIONS LINE 15 IS TAKING THE CROSS |
| VENTILATION CREDIT, SEE 2004 FBC 13-607.1.A.3.1 AND |
| EXPLAIN THIS HOUSE APPLIES OR CORRECT E-CAL'S. |
| *** 2004 FBC 13-607.1.A.3.1 CROSS VENTILATION CREDIT. |
| HOUSES FOR WHICH CREDIT IS CLAIMED FOR CROSS |
| VENTILATION IN ACCORDANCE WITH THE CRITERIA IN SECTION |
| 13-607.2.A.3.3 SHALL HAVE PROVIDED OPERABLE APERTURE |
| AREAS TOTALING A MINIMUM OF 12 PERCENT OF THE FLOOR |
| AREA OF THE ROOM FOR ALL PRIMARY LIVING AREAS AND MAIN |
| BEDROOMS. |
| INSECT SCREENS SHALL BE PROVIDED FOR ALL WINDOWS AND |
| DOORS TO BE CONSIDERED OPERABLE APERTURE AREA. ALL |
| SCREENED ENTRY DOORS AND INTERIOR DOORS IN THE |
| VENTILATED AREAS SHALL BE PROVIDED WITH EITHER (1) |
| MECHANICALLY ATTACHED DOOR STOPS (OR SIMILAR DEVICES) |
| TO HOLD THE DOOR IN AN OPEN POSITION OR (2) OPERABLE |
| LOUVERS. |
| THE TOTAL APERTURE AREA SHALL BE PROVIDED BY A MINIMUM |
| OF TWO DISTINCT WINDOWS. EACH WINDOW SHALL PROVIDE NOT |
| MORE THAN 70 PERCENT OF THE TOTAL APERTURE AREA. THE |
| WINDOWS (OR SLIDING GLASS DOORS) SHALL BE PLACED IN |
| ADJACENT OR OPPOSITE WALLS. THE WINDOWS MAY BE PLACED |
| ON A SINGLE OUTSIDE WALL IF WING WALLS ARE USED. |
| WHERE WING WALLS ARE INCLUDED IN THE BUILDING DESIGN |
| FOR VENTILATION PURPOSES, THEY SHALL BE PLACED BETWEEN |
| WINDOWS TO CREATE A HIGH-PRESSURE AND A LOW-PRESSURE |
| ZONE ON EACH WINDOW. WING WALLS SHALL EXTEND FROM THE |
| GROUND TO EVE HEIGHT, BE LOCATED ON THE WINDWARD SIDE |
| OF THE BUILDING, AND EXTEND OUTWARD FROM THE BUILDING A |
| DISTANCE AT LEAST EQUAL TO ONE-HALF THE WIDTH OF THE |
| WINDOW. |
| NOTE: THIS TECHNIQUE IS EFFECTIVE ONLY FOR AREAS WHICH |
| EXPERIENCE SIGNIFICANT AND CONTINUOUS WINDS DURING THE |
| COOLING MONTHS. |
| |
| 4)THE JOB ADDRESS NEEDS TO BE ON EACH PAGE ON THE |
| PLANS, SEE 2004 FBC, CITY WPB AMEND. 106.1.3 AND FAC |
| 61G1-16.004(3). |
| |
| 5) PLEASE SHOW SIZE FOR SUPPLY AIR GRILL IN BEDROOM #3 |
| ON MECHANICAL PLANS. |
| |
| 6) PLEASE SHOW THE TOTAL AND SENSIBLE BTU'S FOR THE A/C |
| SYSTEM ON THE MECH. PLANS. |
| |
| MECHANICAL PLAN REVIEW BY; |
| TOM GORDON (561) 805-6729. |
| |
| |