Plan Review Notes
Plan Review Notes For Permit 07060823
Permit Number 07060823
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-27 14:40:55 
  
 *** UNSAT ***
  
  
 1) NOTE: PLEASE SEE PLANS ARE MISSING THE FOLLOWING
 REQUIRED CODES TO BE STATED ON PLANS AND FOR DESIGN.
 PLEASE SEE THE FOLLOWING WHICH WAS ADOPTED AS OF
 DECEMBER 8TH, 2006.
 2004 FBC W/2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE KNOW THE PLANS WILL BE ROUTED TO THE
 ADDRESSING REVIEWER AS THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE DOES NOT INDICATE AND ADDRESS, OUR
 SYSTEM SHOWS 1571 6TH ST AND THE PLANS DO NOT INDICATE
 ANY ADDRESS.
 PLEASE KNOW ONCE THE ADDRESS HAS BEEN DECIDED AND
 CORRECTED, PLEASE REVISED TITLE BLOCKS OF PLANS
 ACCORDINGLY.
 FAC61G1-16.004
  
 3) NOTE: PLEASE SEE THE VALUE FOR COMPLETE SCOPE OF
 WORK SHALL BE BASED ON THE FBC AND THE ADOPTED
 SUPPORTING DOCUMENTS. PLEASE SEE THE VALUE SHALL
 INCLUDE ALL LABOR, MATERIALS, EQUIPMENT, DESIGN COST
 ETC AS STATED IN THE FBC 108.3
 PLEASE SEE THIS INCLUDES EQUIPMENT, MATERIALS ETC EVEN
 IF OWNER SUPPLIED. PLEASE SEE THE VALUE WILL BE
 ADJUSTED.
  
 4) NOTE: PLEASE SEE THE PERMIT IS BEING APPLIED AS
 OWNER/ BUILDER WHERE THE PALM BEACH COUNTY PROPERTY
 APPRAISER'S OFFICE ALREADY LIST THIS OWNER NOT ONLY ON
 SEVERAL OTHER PROPERTIES BUT ALSO WITH HOMESTEAD
 EXEMPTION LISTED ON MORE THEN ONE PROPERTY WHICH IS NOT
 PERMITTED UNDER FLORIDA LAW. PLEASE SEE THIS
 INFORMATION FOR MULTIPLE HOMESTEADS WILL BE FORWARDED
 TO THE PBCPA OFFICE.
 PLEASE SEE THAT IN ORDER TO PULL AN OWNER/BUILDER
 PERMIT YOU MUST MEET THE EXCEPTION UNDER FS 489. PLEASE
 KNOW THIS MAY AFFECT THE PERMIT AS APPLIED AND A
 CONTRACTOR MAY BE REQUIRED. INFORMATION MAY ALSO BE
 FORWARDED TO THE COUNTY AND STATE LICENSING BOARD FOR
 REVIEW.
  
 5) NOTE: PLEASE CLARIFY THE MAIN DISCONNECT AS REQUIRED
 PER 230.70,230.71.
 PLEASE SEE THE RISER MENTIONS A MAIN @ PANEL HOWEVER AS
 THE LOCATION OF THE PANEL IS NOT SHOWN, IT CAN NOT BE
 DETERMINED AT THIS TIME IF CODE COMPLIANCE IS MET.
 PLEASE ALSO SEE NEXT COMMENT.
  
 6) NOTE: PLEASE SHOW THE LOCATION(S) OF ALL SERVICE
 EQUIPMENT AND PANEL(S).
 110.26,240.24,408.7 ETC
 FBC 106.3.5.4
  
 7) NOTE: PLEASE INDICATE THE AIC RATINGS ON NEW RISER
 AS THE NOTED RATING ABOVE PANEL SCHEDULE MAY CHANGE
 ONCE THE RISER IS REVISED. 110.9
  
 8) NOTE: PLEASE SEE MISSING THE RECEPTACLE FOR THE
 DISHWASHER AS THE PLANS ONLY APPEAR TO SHOW A COUNTER
 SPACE RECEPTACLE AND THE PANEL SCHEDULE DOES SHOW AS
 DISHWASHER CIRCUIT.
  
 9) NOTE: PLEASE SEE THE MISSING RECEPTACLE FOR THE
 MICROWAVE WHICH IS LISTED ON LOAD CALCULATIONS BUT NOT
 SHOWN ON PLANS.
 408.4, FBC 106.1.2, 106.3.5.4
  
 10) NOTE: PLEASE SEE 210.52B1, 210.11C1 AND 220.53 AS
 THE LOADS FOR ALL SMALL APPLIANCE AND DINING ROOM
 CIRCUITS SHALL BE FIGURED INTO THE LOAD CALCULATIONS.
 PLEASE CLARIFY THE DINING ROOM/AREA.
  
 11) NOTE: PLEASE SEE THE PLANS NEEDS TO SHOW ALL
 LOCATION AND IDENTIFY THE LOCATIONS OF THE AHU AND
 WATER HEATER.
 PLANS INDICATE A 220 RECEPTACLE FOR THE WATER HEATER
 WHICH IS NOT PERMITTED.422.30
 PLEASE SEE MISSING DISCONNECTS PER 440.11 AND 422.31
  
 12) NOTE: PLEASE SEE 422.13 UNDER THE 2005 NEC AS THE
 WATER HEATER NEEDS TO BE SHOWN AT 125%.
  
 13) NOTE: PLEASE SHOW DISCONNECT REQUIRED FOR THE CU.
 440.11
 FBC 106.3.5.4
  
 14) NOTE: PLEASE SEE THE PANEL SCHEDULE SHALL BE
 SPECIFIC FOR ALL CIRCUIT NUMBERS AND DESIGNATIONS ON
 EACH CIRCUIT SHALL BE SPECIFIC TO ALL ROOMS AND AREAS
 IN WHICH THEY FEED.
 PLEASE PLACE THE ROOM AND AREA DESIGNATIONS ON PLANS
 FOR COORDINATION OF CIRCUITS REQUIRED.
 LISTING THE NUMERICAL DESIGNATIONS AS SHOWN IS NOT
 ACCEPTABLE AND LISTING THE GENERAL LTS AND RECEPTS MAY
 NOT BE USED. PLEASE SEE THE FOLLOWING TEXT WHICH HAS
 BEEN EXTRACTED DIRECTLY FROM THE NEC IN 408.4. *SECTION
 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE THAT THE
 IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A
 PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE
 THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED.
 CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED
 AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE
 BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN,
 DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE
 CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT
 ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS
 ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR
 RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT
 OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE
 ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT
 PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS
 SECTION.*
 408.4, 310.16, 240.4 ETC
 FBC 106.3.5.4
  
 15) NOTE: PLEASE LIST THE REQUIRED ARC FAULT PROTECTED
 CIRCUITS ON PANEL SCHEDULE. PLEASE SEE THE PANEL
 SCHEDULE ONLY INDICATES ONE ARC FAULT CIRCUIT WHICH IS
 NOT POSSIBLE.
 210.12, 408.4
  
 16) NOTE: PLEASE INDICATE THE TYPE OF RECESSED LIGHTS
 PER FBC 13-606.1.ABC.1.2.4
  
 17) NOTE: PLEASE SEE MISSING SOME TYPE OF LIGHT FIXTURE
 OR SWITCHED RECEPTACLE IN ROOMS. THE USE OF A FAN J-BOX
 IS NOT ACCEPTABLE. IF A FAN/ LT IS GOING TO BE CHOSEN,
 THESE MUST BE SHOWN ON PLANS AT THIS TIME AND THEY WILL
 BE REQUIRED TO BE INSTALLED BEFORE FINAL.
 THE SWITCHING OF A HALF SWITCHED RECEPTACLE IS ALSO
 PERMITTED.
 PLEASE SEE 210.70 , HOWEVER ALSO LS 101 7.8 .
  
 18) NOTE: PLEASE SEE MISSING REQUIRE DEDICATED BATH(S)
 CIRCUIT(S) PER 210.11C3. MUST BE 20A AND #12.
  
 19) NOTE: NOTE: PLEASE SEE PLANS AND PANEL SCHEDULE
 INDICATE SMOKE DEVICES AS *SD* AND SYMBOL LEGEND HAS
 THESE AS SMOKE DETECTORS.
 PLEASE KNOW THAT A MEETING WAS HELD AT THE SOUTHERN
 SECTION MEETING IN OCT 06 WHERE ALL WERE DIRECTLY
 INFORMED BY NFPA THAT THE USE OF SD FOR SMOKE DETECTORS
 ON PLANS FOR RESIDENTIAL HOMES IS NOT ACCEPTABLE WHEN
 THESE DEVICES ANY ACTUALLY FALL UNDER THE DEFINITIONS
 OF SMOKE ALARMS WHICH WOULD BE SHOWN AS SA/SMOKE
 ALARMS.
  
 BY THE DEFINITIONS AS STATED IN NFPA-72 A SD/ SMOKE
 DETECTOR IS ONLY A DEVICE WHICH WILL DETECT AND WILL
 NOT SOUND AN AUDIBLE ALARM. THIS WOULD BE DONE BY
 HORN/SIREN TYPE DEVICES. PLEASE SEE THE DEFINITIONS OF
 SA/SMOKE ALARMS; THESE ARE DEVICES WHICH ARE 120V (AS
 SHOWN) AND WOULD DETECT AND SOUND AN ALARM. THIS IS
 SOMETHING THAT IS NOW BEING COMMENTED ON OTHER REVIEWS
 FOR OTHER NEW HOMES.
 AS SHOWN ON PLANS AND NOTED THESE SHOULD INDEED BY SA
 FOR SMOKE ALARMS.
 ** PLEASE SEE THAT SMOKE ALARMS ARE STATED IN THE FBC
 RESIDENTIAL CODE/ FBC AND IN NFPA-72.
 IF THERE ARE ANY QUESTIONS ON THIS COMMENT PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE*.
 PLEASE SEE NFPA-72 11.5.1.1, 11.8.3
  
 20) NOTE: PLEASE SEE PLANS ARE NOT SIGNED, DATED AND
 SEALED BY ANY DESIGNER OF RECORD OR DESIGN
 PROFESSIONAL. FS 481.229, 471.003 ETC
 PLEASE SEE THE TITLE BLOCK INDICATES HOMES DESIGNED BY
 ETC HOWEVER NO LICENSE INFORMATION WAS STATED ON TILE
 BLOCKS FOR SAID FIRM. FAC 61G1-16.004, 61G15-23.002, FS
 481.219 AND 471.023.
 PLEASE SEE THE PLANS EVEN STATE * NOT VALID WITHOUT
 SEAL*.
  
 21) NOTE: PLEASE SEE MISSING RECEPTACLE PER 210.52. SEE
 REDLINED PLANS.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT SHOWN OR
 SUBMITTED FOR REVIEW, THE REVIEW FOR CODE COMPLIANCE
 CAN ONLY BE BASED ON THE PLANS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** PLEASE BE SURE TO SEE ANY COMMENTS FROM OTHER TRADES
 WHICH MAY AFFECT ELECTRICAL PLANS AND DESIGN CHANGES.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]