2007-07-16 08:30:39 | DENIED BY BUILDING |
| |
| 1) IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) A RECORDED COPY OF THE NOTICE OF |
| COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| PERMIT CAN BE ISSUED. |
| |
| 3) SUBMIT A DRAINAGE PLAN SHOWING COMPLIANCE WITH FBC R |
| 401.3. SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM |
| SEWER CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION |
| SO AS NOT TO CREATE A HAZARD. LOTS SHALL BE GRADED SO |
| AS TO DRAIN SURFACE WATER AWAY FROM FOUNDATION WALLS. |
| THE GRADE AWAY FROM FOUNDATION WALLS SHALL FALL A |
| MINIMUM OF 6 INCHES WITHIN THE FIRST 10 FEET. |
| |
| 4) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| SIGNED BY THE OWNER/ AGENT PER FBC CHAPTER 13. |
| |
| 5) SHOW COMLIANCE WITH FBC R 309.1 AND 309.2 FOR |
| OPENING PROTECTION (DOOR REQUIREMENTS) AND GARAGE |
| SEPARATION (WALL REQUIREMENTS). |
| |
| 6) ON SHEET 3 THE EDITION OF SOME OF THE STANDARDS THAT |
| WERE SPECIFIED ARE INCORRECT. IN ORDER TO COMPLY WITH |
| THE EDITION OF THE STANDARDS REFERENCED IN THE 2004 |
| FBC, PLEASE UPDATE TO ACI 530-02/ ASCE 7-02 AND TMS |
| 402-02. |
| |
| 7) REVISE THE ROOF SHEATHING NAILING SCHEDULE ON SHEET |
| 4. THE CORNERS OF HIP ROOFS ARE ALSO ZONE 3. SEE |
| DIAGRAM FBC R301.2(8).R 803.2.3.1 REQUIRES 8D RING |
| SHANK NAILS FOR ALL ROOF ZONES. |
| |
| 8) TWO COPIES OF ALL PRODUCT APPROVALS ARE REQUIRED. |
| PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE STATE APPROVAL, BUT |
| HAS A MIAMI-DADE NOA, THE NOA IS ACCEPTABLE BY ITSELF. |
| |
| 9) THE WINDOW SCHEDULE ON SHEET 2 HAS WINDOWS LISTED |
| THAT ARE NOT USED IN THIS PROJECT. REVISE THE SCHEDULES |
| TO ONLY LIST INFORMATION THAT PERTAINS TO THIS |
| PROJECT. |
| |
| 10) SUBMIT PRODUCT APPROVALS FOR THE FOLLOWING: |
| - SINGLE HUNG WINDOWS |
| - ARCHED FIXED GLASS WINDOWS |
| |
| 11) THE PRODUCT APPROVAL FOR THE GAF SHINGLES HAVE BEEN |
| REVISED. SUBMIT THE NEW STATE COVERSHEET AND THE NEW |
| NOA # 05-1115.08. |
| |
| 12) THE PRODUCT APPROVAL SUBMITTED FOR THE MASONITE |
| DOOR, FL 19 IS NO LONGER VALID. |
| |
| 13) SUBMIT PRODUCT APPROVALS FOR THE OVERHEAD GARAGE |
| DOORS. |
| |
| 14) SUBMIT AN INSTALLATION SCHEDULE FOR THE STORM |
| PANELS. SPECIFY THE CONNECTION/MOUNT TYPE, THE ANCHOR |
| TYPES, THE ANCHOR SPACINGS, ETC.SEE ATTACHED. |
| |