2007-07-11 17:01:16 | DENIED |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. THE INDICATEDLONGEST LENGTH OF THE EXISTING GAS |
| SYSTEM IS BEING INDICATED AS FIFTY FEET (50'). THE |
| PROPOSED PIPING DISTANCE TO THE GRILL IS BEING |
| INDICATED AS ANOTHER FIVE FEET (5'). THATS A LONGEST |
| LENGTH TOTAL OF FIFTY FIVE FEET (55'). THE EXISTING |
| PIPING TO THE GRILL IS BEING INDICATED AS 1/2" |
| GALVANIZED. PER FBC-2004 FUEL GAS TABLE 402.4(2) THE |
| 1/2" GALVANIZED PIPING IS ONLY GOOD FOR 66,000 BTU'S. |
| THE PROPOSED GRILL IS 90,000 BTU'S. THIS WILL NOT WORK |
| AS 0.5 PSI DELIVERY PRESSURE. THE OPTIONS ARE (A) |
| INCREASE THE EXISTING 1/2" GALVANIZED PIPE SIZE TO |
| 3/4". (B) RESUBMIT WITH A 2 PSI DELIVERY PRESSURE. |
| PLEASE INCLUDE MANUFACTURER SPECIFICATIONS FOR THE |
| PROPOSED MP REGULATORS WITH THE MAKE, MODEL NUMBER, |
| LOAD CAPACITY AND A LISTING FROM A NATIONALLY |
| RECOGNIZED TESTING LABORATORY [NRTL]. PLEASE CLEARLY |
| INDICATE THE LOCATION OF THE MP REGULATORS ON THE |
| RESUBMITTED DRAWING. (C) CHANGE THE GRILL TO ACCOMODATE |
| THE BTU LOAD OF THE EXISTING 1/2" GALVANIZED GAS |
| PIPING. |
| NOTE: PLEASE CLEARLY INDICATE THE LONGEST LENGTH OF THE |
| EXISTING SYSTEM FROM THE METER TO THE FARTHEST |
| APPLIANCE ON THE RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS EXAMINER |