2007-07-31 14:35:20****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.)SEE OPENING 5.FBC R TABLE 301.2(2) AND 301.2(3)
 REQUIRE A DESIGN PRESSURE OF -38.2 FOR 10SF, MULTIPLIED
 BY 1.29 FOR MRH OF 20', EXPOSURE C, FOR A DESIGN
 PRESSURE OF -49.28.YOU ARE DESIGNING TO -45PSF.YOUR
 PRODUCT APPROVAL REQUIRES USE OF THE -77PSF ROW FOR
 PRESSURES OVER -47.2, SO THE ANCHOR SPACING OF 6"/6" IS
 NOT COMPLIANT FOR THIS OPENING.
  
 CHECK ALL OPENINGS.THIS COMMENT APPLIES TO OTHER
 OPENINGS.YOU MUST DESIGN USING EITHER FBC TABLE
 R301.2.1(2) AND (3), FBC R 301, OR WITH AN ARCHITECT OR
 ENGINEER USING ASCE7-02.
  