Plan Review Notes
Plan Review Notes For Permit 07060788
Permit Number 07060788
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-10 16:14:08****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)THE INSTALLATION SCHEDULE IS NOT REQUIRED FOR THE
 WINDOWS.
  
 2.)OPENINGS 20, 22, 23, DESIGN PRESSURE GREATER THAN
 -31.2 REQUIRES USE OF THE -47.2 ROW.ANCHOR SPACING ON
 THE INSTALLATION SCHEDULE IS NOT COMPLIANT FOR THESE
 OPENINGS.
  
 3.)PLEASE EXPLAIN HOW THE SPAN IS THE SAME AS THE
 OPENING SIZE WITH A 3" EDGE DISTANCE.
  
 4.)PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.CODE COMPLIANCE
 CANNOT BE DETERMINED FROM THE INFORMATION PROVIDED.