Plan Review Notes
Plan Review Notes For Permit 07060787
Permit Number 07060787
Review Stop B
Sequence Number 1
Notes
Date Text
2007-07-06 17:03:38****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.THE DESIGN PRESSURES SPECIFIED CANNOT BE LESS THAN
 FBC R TABLE 301.2(2), TABLE 301.2(3).
  
 2.REVISE EXPOSURE CATEGORY FBC1609.6.2.1(2), FBC
 R301.2.1.4.NOTE THAT THE DEFINITION FOR EXPOSURE C
 HAS CHANGED EFFECTIVE DECEMBER 8, 2006 FBC1609.4, FBC
 R301.2.1.4.REVISE ANCHOR SPACING AS NECESSARY.
  
 3.PROVIDE A FLOOR PLAN SHOWING: WINDOW LOCATIONS,
 SIZES, WINDOW TYPE, ROOM DESIGNATIONS.NOTE EXISTING
 CONDITIONS (TYPE OF WINDOW) AND OPENING SIZE FOR
 BEDROOMS, FBC R310, FBC EB 505.1.
  
 4.THE INSTALLATION SCHEDULE IS FOR SHUTTERS.
 OPENINGS 1 THROUGH 14 ARE IMPACT WINDOWS, BUT ARE
 INCLUDED ON THE INSTALLATION SCHEDULE.PLEASE CLARIFY
 SCOPE OF WORK.
  
 5.THE APPLICATION STATES THAT 2 S. PANELS (STORM
 PANELS?) WILL BE INSTALLED.PLEASE PROVIDE PRODUCT
 APPROVALS