Plan Review Notes For Permit 07060773 |
Permit Number |
07060773 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-07-09 08:27:35 | DENIED; | | 1. FLOOR DRAIN SHOULD BE A WASTE RECEPTOR WITH AN | | INTERIOR STRAINER. FBC-2004 PLUMBING SECTIONS 802.2 AND | | 802.3. | | 2. WATER HAMMER ARRESTOR IS REQUIRED ON HOT WATER TO | | THE DISHWASHER. SECTION 604.9 | | 3. BREAK SINK TO MEET ACCESSIBILITY CODE SECTIONS | | 11-4.24.1 THRU 11-4.23.7 | | A) 11-4.24.3 THE FRONT OF CABINET TO BE | | OPEN FOR KNEE CLEARANCE OF 19" UNDER SINK. ALSO THE | | GARBAGE DISPOSAL MUST BE OFF SET OR DELETED. | | B) 11-4.24.4 DEPTH OF SINK TO BE A MAXIMUM | | OF 6 1/2" DEEP. ( SHOW ON PLANS) | | C) EXPOSED PIPES TO BE INSULATED. | | PLUMBING PLAN REVIEW BY: | | JOHN LEECH | | 805-6695 |
|