Plan Review Notes
Plan Review Notes For Permit 07060773
Permit Number 07060773
Review Stop E
Sequence Number 1
Notes
Date Text
2007-06-29 15:04:36 
  
  
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} THE EMERGENCY BATTERY PACK MUST BE ON CIRCUIT P1-15
 TO COMPLY WITH 700-12(F)(4) "THE BRANCH CIRCUIT FEEDING
 THE UNIT EQUIPMENT SHALL BE THE SAME BRANCH CIRCUIT AS
 THAT SERVING THE NORMAL LIGHTING IN THE AREA AND
 CONNECTED AHEAD OF ANY LOCAL SWITCHES."
  
 2} CIRCUITS 67, 69,AND 73ON THE PANEL SCHEDULE DO
 NOT CORRELATE WITH THE EQUIPMENT SHOWN ON THE PLAN,
 SHEET E-1.1.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718