2007-11-06 14:04:25 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBCFLORIDA BUILDING CODE 2004 |
| FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| CODE |
| FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| FAC FLORIDA ADMINISTRATIVE CODE |
| FSFLORIDA STATUTE |
| |
| FROM PREVIOUS LISTS: |
| |
| 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE |
| SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE |
| OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE |
| APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE |
| INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A |
| PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO |
| [email protected] DO NOT SUBMIT THIS PLAN WITH THE |
| PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE |
| RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS |
| COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE |
| CONTACT ME IF YOU NEED FURTHER INFORMATION. |
| |
| PLANS CANNOT BE APPROVED AS IS UNTIL THIS REQUIREMENT |
| IS MET.ENGINEER STATED IN HIS RESPONSE LETTER THAT |
| THE SHUTTERS WILL BE STORED "VIA STRAPPING".A DETAIL |
| SHOULD BE PROVIDED WITH THE INSTALLATION PLAN.THE |
| ATTACHED INSTALLATION SCHEDULE IS REQUIRED OR A |
| SEPARATE PERMIT WILL BE REQUIRED FOR THE SHUTTERS. |
| |
| NEW COMMENTS: |
| |
| THE PLANS APPEAR TO BE A LEVEL 2 ALTERATION DUE TO THE |
| CONSTRUCTION OF THE NEW STAIRS.IF THIS STAIRS ARE |
| EXISTING AND BEING REBUILT (NO RECONFIGURATION OF |
| SPACE), PLEASE NOTE THIS ON THE PLAN.THIS MAY BE |
| WRITTEN AND INITIALED BY THE ENGINEER (NO NEW SHEETS |
| REQUIRED). |
| |
| |