2007-11-06 14:04:25****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LISTS:
  
 18.)SEE ATTACHED POLICY IN REGARDS TO HURRICANE
 SHUTTERS, ITEM 13.SUBMIT AN INSTALLATION PLAN.USE
 OF REMOVABLE SHUTTERS ON COMMERCIAL BUILDINGS MUST BE
 APPROVED BY THE BUILDING OFFICIAL.THIS MAY BE DONE
 INDEPENDENTLY FROM THE PLAN REVIEW PROCESS AND A
 PRELIMINARY PLAN CAN BE SUBMITTED VIA EMAIL TO
 [email protected] DO NOT SUBMIT THIS PLAN WITH THE
 PERMIT APPLICATION RESUBMITTAL AS THIS SHOULD BE
 RESOLVED PRIOR TO RESUBMITTAL.FAILURE TO ADDRESS THIS
 COMMENT WILL RESULT IN DELAYS IN PERMITTING.PLEASE
 CONTACT ME IF YOU NEED FURTHER INFORMATION.
  
 PLANS CANNOT BE APPROVED AS IS UNTIL THIS REQUIREMENT
 IS MET.ENGINEER STATED IN HIS RESPONSE LETTER THAT
 THE SHUTTERS WILL BE STORED "VIA STRAPPING".A DETAIL
 SHOULD BE PROVIDED WITH THE INSTALLATION PLAN.THE
 ATTACHED INSTALLATION SCHEDULE IS REQUIRED OR A
 SEPARATE PERMIT WILL BE REQUIRED FOR THE SHUTTERS.
  
 NEW COMMENTS:
  
 THE PLANS APPEAR TO BE A LEVEL 2 ALTERATION DUE TO THE
 CONSTRUCTION OF THE NEW STAIRS.IF THIS STAIRS ARE
 EXISTING AND BEING REBUILT (NO RECONFIGURATION OF
 SPACE), PLEASE NOTE THIS ON THE PLAN.THIS MAY BE
 WRITTEN AND INITIALED BY THE ENGINEER (NO NEW SHEETS
 REQUIRED).
  
  